Appendix B <br />(TYPE) AUTO LIMITER II Overfill Valve In Tank Shut Off Level Worksheet <br />`'.Important: This is meant to be a supplemental worksheet and not a substitute to following the installation <br />manual instructions. All length measurements are in inches. Please contact the Authority Having Jurisdiction <br />(AHJ) and review local, state, and national codes to determine the regulatory requirements governing shut-off, <br />capacity in your region, as well as take into account other considerations such as extreme tank tilt. <br />Take the following measurements with the valve <br />Installed in the tank: <br />Upper tube to shut off point on valve. <br />(D) = 47 <br />(VII) = 127 <br />(U)= 125 <br />Top of tube flange to tank bottom. <br />(B) = 130 <br />From the tank calibration chart: provided by tank <br />manufacturer find the dipstick number (Y) which <br />corresponds to the 100% volume. <br />(Y) = 9,842------ <br />1. To determine shut-off percentage: <br />Subtract upper tube length (D) from distance to <br />tank bottom (B) <br />(X) = (B) — (D) - 2" _ (OPW) <br />(X) = (B) --- (D) = 83 (Other) <br />Using the tank calibration chart provided by the <br />tank manufacturer determine the tank capacity at <br />the calculated (X) dimension and the 100% volume <br />(Y) tank capacity. <br />(X) tank capacity in gallons = 9,299 <br />(Y) tank capacity in gallons = _ 9,842 <br />SO% = (X) capacity I (Y) capacity x 100 = 94.4% <br />FACILITY: (TANK 1 PREMIUM) <br />iCHEVRON <br />6633 PACIFIC AVENUE <br />STOCKTON, CSA 95207 <br />NOTES: Valve was removed and functional. <br />i <br />I <br />O <br />i <br />(a) <br />Upper <br />Tube <br />i <br />i <br />(w) <br />Valve,; <br />Length, <br />bottom of <br />cut i r <br />(g) <br />To Tank <br />ti <br />(u) (Y) ll <br />Valve Tank t <br />I Length, Chartf <br />top of cut _ 100% <br />Volume <br />Dipstick <br />Note: The overfill valve must be installed per AHJ <br />requirements and all applicable local, state, and national <br />codes. If oveifll valve is set above the allowable shut-off. <br />percentage the overfill valve must be removed and <br />replaced. For reference 40 CFR part 280 Subpart B Section <br />280.20 overfill valves should be set to a maximum of 95%_ <br />