Laserfiche WebLink
SWRCB,January 2002 FINAL DRAFT Page 2 of 4 <br /> 4. TANK ANNULAR TESTING <br /> Test Method Developed By: ®Tank Manufacturer ® Industry Standard ❑ Professional Engineer <br /> ❑Other(Spec) <br /> Test Method Used: ❑Pressure ® Vacuum ❑Hydrostatic <br /> ❑Other(Specify) <br /> Test Equipment Used: 0 to 30"hg Dial Gauge Equipment Resolution: 21/o@ Mid <br /> Tank# Tank# Tank# Tank# <br /> DIESEL <br /> Is Tank Exempt From Testing?' ❑Yes ®No ❑Yes [:]No ❑Yes ❑No ❑Yes ❑No <br /> Tank Capacity: 1500g <br /> Tank Material: Steel/Fiberglass <br /> Tank Manufacturer: Modern Welding <br /> Product Stored: Diesel <br /> Wait time between applying <br /> pressure/vacuum/water and 10 minutes <br /> starting test: <br /> Test Start Time: 2:03p <br /> Initial Reading(R,): 10.00"hg <br /> Test End Time: 3:28p <br /> Final Reading(RF): 10.00"hg <br /> Test Duration: 85 minutes <br /> Change in Reading(RF-RI): 0.00"hg <br /> Pass/Fail Threshold or Criteria: 0.00"hg <br /> Test Result ®Pass ❑Fail ` ❑Pass []Fail []Pass ❑Fail []Pass []Fail <br /> Was sensor removed for testing? ®Yes❑No ❑NA ❑Yes❑No[INA ❑Yes❑No ❑NA ❑Yes❑No❑NA <br /> Was sensor properly replaced and ®yes❑No [:]NA ❑Yes❑No❑NA ❑Yes ONO❑NA ❑Yes❑No❑NA <br /> verified functional after testin ? <br /> Comments—(Include information on repairs made prior to testing,and recommended follow-up for failed tests.) <br /> This is an Emergency Generator Tank. <br /> ' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. {California Code of Regulations,Title 23, Section 2637(a)(6)) <br />