Laserfiche WebLink
Doug Baker <br /> September 22, 2003 <br /> Page 2 <br /> 6. Machinery and equipment utilizing hazardous materials shall be anchored by <br /> Building Code requirements. Some tanks are sifting on cement blocks and are <br /> not secured. CFC. Sec. 8001.4.8 <br /> 7. Provide hazard identification signs on stationary containers and tanks for <br /> specified materials they contain. CFC. Sec. 8001.8 <br /> 8. Remove the extension cords and replace with permanent wiring through the <br /> area. CFC, Sec. 8506 <br /> 9. Remove the buildup of chemical waste from electrical motors. These motors shall <br /> be free from accumulations of oil, dirt, waste and other debris, which will interfere <br /> with required motor ventilation or create a fire hazard. CFC, Sec. 850.5 <br /> Waste Treatment Area <br /> 1 Provide signage in the dispensing and open-use areas and within 25 feet of the <br /> outdoor dispensing or open-use area that read "No Smoking". CFC, Sec. <br /> 8004.1.8 <br /> 2. The secondary containment system in the Treatment Area has major degrading <br /> and cracking of the flooring and is therefore no longer liquid tight. Repair or if <br /> needed replace the secondary containment and apply a coating to maintain its <br /> integrity. The secondary containment shall be of liquid-tight construction. CFC, <br /> Sec. 8004.2.2.5.2 and 8003.1.3.3 <br /> 3. Label all piping and tubing that convey material. CFC, Sec. 8001.4.3.2 <br /> 4. Repair defective equipment and tanks. Equipment, machinery and systems <br /> associated with hazardous materials shall be maintained in an operable <br /> condition. Defective containers, cylinders and tanks shall be removed from <br /> service, repaired or disposed of in an approved manner. Defective equipment or <br /> machinery shall be removed from service and repaired or replaced. CFC. Sec. <br /> 8001.4.7.1 <br /> 5. Machinery and equipment utilizing hazardous materials shall be anchored by <br /> Building Code requirements. Some of the tanks in the secondary containment <br /> are on blocks and are not secured. CFC. Sec. 8001.4.8 <br /> 6. Provide identification signs on stationary containers and tanks for specified <br /> materials they contain. CFC. Sec. 8001.8 <br /> 7. Remove all extension cords and replace damaged wiring in this area. CFC, Sec. <br /> 8504 and 8506 <br /> 8. Electrical motors shall be maintained free from accumulations of dirt, waste, oil <br /> and other debris which will interfere with required motor ventilation and create a <br /> fire. Remove the buildup of chemical waste. CFC, Sec. 8505 <br />