Laserfiche WebLink
RECEIVED <br /> SWRCB,January 2002 Page of <br /> Xm <br /> 4. TANK ANNULAR TESTING <br /> Test Method Developed By: X Tank Manufacturer ❑Industry Standard ❑ i <br /> ❑Other(Specify) <br /> Test Method Used: ❑Pressure X Vacuum ❑Hydrostatic <br /> ❑Other(Spec) <br /> Test Equipment Used: Gast Vacuum Pump/Vacuum Gauges in Hg. Equipment Resolution:- '/2"x-301-1g. <br /> Tank# 1 Tank#2 Tank# Tank# <br /> Is Tank Exempt From Testing?' No No <br /> Tank Capacity: 20K 6K <br /> Tank Material: Fiberglass Fiberglass <br /> Tank Manufacturer: Owens Corning Owens Corning <br /> Product Stored: Diesel Gasoline <br /> Wait time between applying 10 Minutes 10 Minutes <br /> vacuum and starting test: <br /> Test Start Time: 12:40 1:25 <br /> Initial Reading(Rj): -10 Hg. -10 Hg. <br /> Test End Time: 2:40 2:25 <br /> Final Reading(RF): -10 Hg. -10 Hg. <br /> Test Duration: 2 Hours 1 Hour <br /> Change in Reading(RF-RI): 0 Hg. 0 Hg. <br /> Pass/Fail Threshold or Criteria: ➢ -2 Hg. ➢ -2 Hg. <br /> Test Result: Pass Pass <br /> Was sensor removed for testing? No No <br /> Was sensor properly replaced and N/A N/A <br /> verified functional after testing? <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> ' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. {California Code of Regulations,Title 23,Section 2637(a)(6)} <br />