Laserfiche WebLink
S A N X10 A Q U I N Environmental Health Department <br /> AMENDEP <br /> Z3 1 <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> TIWANA GAS&FOOD 1210 E HAMMER LN,STOCKTON June 29,2018 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 103 HSC 25292.2, 25299.30 Current financial responsibility documents not submitted. <br /> Current Financial responsibility documents have not been submitted to the EHD. Current financial responsibility <br /> documents are required to be submitted annually. Financial responsibility documents that have been updated were <br /> last signed on 6/12/2017 and are no longer current. Immediately log into the California Environmental Reporting <br /> System (CERS)at http://cers.calepa.ca.gov/,and upload the required documents. <br /> This is a repeat violation, Class II. <br /> 105 CCR 2632(d)(1), 2634(d)Failed to have an approved UST monitoring plan. <br /> The monitoring plan is not current and/or not approved by the 89 product tank has been converted into the 91 <br /> product tank and the monitoring plan has not been updated on CERS to demonstrate those changes. Different leak <br /> detectors were observed for both tanks. The monitoring plan must be uploaded to the California Environmental <br /> Reporting System(CERS). Immediately log into CERS, make the necessary changes,and submit for review by the <br /> EHD. <br /> This is a repeat violation, Class II. <br /> 111 CCR 2638(a)Failed to test monitoring and leak detection equipment annually. <br /> The 91 product leak detector testing were last performed on 6/13/2016 and was due by June 2017. Testing has not <br /> been completed and is 24 months past due. These tests are required once every 12 months. Immediately <br /> schedule these tests and provide 48 hours notification to the EHD. Please be aware that a follow up inspection will <br /> be charged at our current hourly rate. <br /> This is a repeat violation, Class II. <br /> 113 CCR 2638(d)Failed to submit monitoring system certification test report within 30 days. <br /> Annual monitoring system certification, leak detector testing, and spill container testing was performed on 6/26/17 <br /> and a test report was submitted on 12/04/17 , 4 months late. A copy of the test report must be submitted within 30 <br /> days of the tests. Take all necessary precautions to ensure testing and submittal of test reports are performed in a <br /> timely manner. <br /> This is a Class II violation. <br /> 121 CCR 2712(f)Failed to submit a written response within 30 days of receiving an inspection report. <br /> An inspection was last done on 6/26/17 and an inspection report was issued identifying information to be submitted <br /> to bring this site into compliance. This information was required to be submitted by 7/26/17. This information was <br /> received on 1/19/18, 5 months late, resulting in a non-compliant status for this facility. An operator that receives an <br /> inspection report shall have 30 days to submit a written response that includes a statement documenting corrective <br /> actions taken or proposing corrective actions which will be taken. Ensure that a written response documenting <br /> corrective actions taken or proposed is submitted within 30 days of receiving an inspection report. <br /> This is a Class II violation. <br /> FA0003730 PR0231125 SC001 06/29/2018 <br /> EHD 23-01 Rev.10/31/2017 Page 4 of 8 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />