Laserfiche WebLink
• 0 <br />PRODUCT PIPING SUMP TESTING <br />Test Method By: 0 Manufacturer • industry Standard o Professional Engr o Other (see below) <br />Test Method Uses: O Pressure 0 Vacuum • Hydrostatic o Other (see below) <br />Measuring Equipment Used: 1NCON TS -STS (Electronic Sump Test System) <br />Description <br />Tank #1 <br />Tank #2 Tank #3 Tank #4 <br />Tank product <br />- -- <br />Gasoline - 91 <br />Gasoline - 89 Gasoline - 87 Diesel <br />Sump malarial <br />FRP <br />FRP FRP FRP <br />Sump diameter (inches) <br />48 <br />Sump depth (inches) <br />86 <br />Haight from tank top to highest <br />P� penetration (inches) <br />18 <br />Height from tank top to lowest <br />electrical tion (Inches) <br />16 <br />od <br />Methof sump attsctnrn►rut to tank <br />Condition of surrlp prior to Grating <br />Yank Collar <br />Dry <br />" <br />Portion of sump tested <br />Entire <br />-- <br />testing? <br />Yes_-- <br />Is system renpned for feti-sate operation? <br />Unknown <br />_ <br />Was tail -este verified to be operationalT <br />No <br />?v <br />Was sensor removed for tea" <br />Yea <br />properly <br />Was sensor aced after <br />_ieplh of water love frau tank top (inches) <br />Welt time for water level to statrilize (humin) <br />21 <br />0:06 <br />Test start lane <br />4:27 PM <br />� ry <br />Initial Probe Readap <br />5.06WTest <br />end time <br />4:43 PM <br />Feral Probe Reading <br />6.0809 <br />-- - <br />Test duration (humin) <br />016�----- <br />_ �—T -- <br />Changs in water level (10.0000 inches} <br />0.0004 <br />Pass/Fad threshold (10.0020 Inches ! } Hr.) <br />0.0020 <br />— <br />TEST RESULT <br />PASS <br />Comments: <br />" <br />testing? <br />Yes_-- <br />