11lei ls •im' i*l <br />Initial: <br />Dlr.�--- <br />Arco. <br />ARCO Facility• ..09 <br />Manual tank gauging will be performed in accordance with the details of Section 2645, <br />instructions:4. Title 23, CCR (copy attached and hereby incorporated). <br />OPERATOR RESPONSIBILITIES <br />At a minimum, the OPERATOR will conduct gauging weekly according to the following <br />A. Tank liquid level measurements shall be taken at the beginning and ending of a gauging <br />period which shall be at least 36 continuous hours during which no liquid is added to or <br />removed from the tank. Record measurements on gauging log(Exhibit:• <br />B. The underground storage tank shall be secured to prevent inputs or withdrawals during <br />the gauging period. No inputs shall occur within the 12 -hour period preceding the <br />gauging period. <br />CL The liquid level measurements shall be based on an average of two consecutive stil <br />readings at both the beginning and ending of the period. <br />D. Measure the level of the product over the full range of • • the nearest <br />one-eighth of <br />E. If the variation between beginning and ending measurements exceeds the weekly or <br />monthly standards (Exhibit B); a second 36 hour test shall be commenced <br />immediately and all measurements and calculations checked for possible errors. If the <br />second test confirms a variation: • the weekly or monthly standards, <br />