Laserfiche WebLink
FORM AF4 <br /> TANK OWNERS COMPLIANCE GUIDE <br /> NOTE: OWNER, LOCAL AUTHORITY, OR IMPLEMENTING AGENCY MAY USE THIS <br /> FORM AS A GUIDELINE FOR INSPECTION. UNDER APPLICABLE FEDERAL LAW, <br /> THE TANK OWNER IS RESPONSIBLE TO DEMONSTRATE THAT HIS TANK MEETS <br /> THE UPGRADE REQUIREMENTS. AS NOTED IN NFPA 30, THE OWNER OR HIS <br /> DESIGNATED AGENT MAY BE THE AUTHORITY HAVING JURISDICTION. THE <br /> OWNER MAY USE THIS FORM TO INSURE COMPLIANCE WITH 40 CFR <br /> 280.21(b)(1)(i),280.33(a), and 280.33(d)(1). <br /> FORMS TO BE SUPPLIED TO OWNER BY CONTRACTOR: <br /> Employers confined space entry certification and training form (FORM AFI) -To be <br /> completed prior to work <br /> Inspection Affidavit(FORM AF2)- To be completed after completion of work <br /> SAFETY CHECK: <br /> FRESH AIR MASK <br /> SAFETY WRISTLETTS <br /> EXPLOSION PROOF LIGHT <br /> 5 MINUTE RESCUE AIR PACKS <br /> OXYGEN AND VAPOR MONITORING EQUIPMENT <br /> AIR SAW <br /> AIR DRILL <br /> AUTOMATIC FIRE EXTINGUISHERS <br /> TRAINING MANUAL IN TRUCK <br /> EMERGENCY INFORMATION POSTED ON JOB (SEE FORM AFI) <br /> QUALITY CONTROL CHECK: <br /> Yes-No 1. Sand Sieve or Grit Size= 18 mesh grit <br /> Yes-No 2.Air compressor maintains minimum 90 lb.psi at the blast nozzle and compressor <br /> during abrasive blasting operation. <br /> Yes-No 3. White metal surface preparation (see Figure 5) <br /> Yes-No 4. Thickness tester with factory directions and calibration chip. <br /> Yes-No 5. Did the tank have a nominal thickness of 125 mils and a minimum thickness of no <br /> less than 100 mils (see section A13.1.1) <br /> 26 <br />