Laserfiche WebLink
n <br />SWRCB, January 2002 Page of <br />17. FILL RISER CONTAINMENT SUMP TESTING <br />Facility is Not Equipped With Fill Riser Containment Sums ❑ <br />Fill Riser Containment Sumps are Present, but were Not Tested ❑ <br />Test Method Developed By: ❑ Sump Manufacturer ❑ Industry Standard X Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: ❑ Pressure ❑ Vacuum X Hydrostatic <br />❑ Other (Spec) <br />Test Equipment Used: Caldwell Level Change Indicator Equipment Resolution: .002 <br />Fill Sump#5-Diesel- Fill Sump # Fill Sump # Fill Sump # <br />A -B <br />"Sum2Diame.ter: <br />42" <br />44" <br />Height from Tank Top to Top of <br />Highest Piping Penetration: <br />No Piping <br />Penetrations <br />Height from Tank Top to Lowest <br />Electrical Penetration: <br />14" <br />Condition of sump prior to <br />testing: <br />Dry <br />Portion of Sump Tested <br />Water Line 18" <br />Sump Material: <br />Fiberglass <br />Wait time between applying <br />water and starting test: <br />5 Minutes <br />Test Start Time: <br />10:32 <br />Initial Reading (RI): <br />.001 <br />Test End Time: <br />11:02 <br />Final Reading (RF): <br />.001 <br />Test Duration: <br />30 Minutes <br />Chane in Reading (RF -RI): <br />0 <br />Pass/Fail Threshold or Criteria: <br />.005/30 Minutes <br />Test Result: <br />Pass <br />Is there a sensor in the sump? <br />Yes <br />Does the sensor alarm when <br />either product or water is <br />detected? <br />Yes <br />Was sensor removed for testing? <br />Yes <br />Was sensor properly replaced and <br />verified functional after testing? <br />Yes <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />�nw., <br />