Test Method Developed By: p UDC Manufacturer ® Industry Standard ❑ Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: ❑ Pressure ❑ Vacuum ® Hydrostatic <br />❑ Other (Specify) <br />Test Equipment Used: Ineon Sump Tester Equipment Resolution: +/- 0.002" <br />UDC Manufacturer: <br />UDC #7/8 <br />Bravo <br />UDC Material: <br />Steel <br />UDC Depth: <br />12" <br />Height from UDC Bottom to Top <br />of Highest Piping Penetration: <br />Located on Bottom <br />Height from UDC Bottom to <br />Lowest Electrical Penetration: <br />Located on Bottom <br />Condition of UDC prior to <br />testing: <br />Good <br />Portion of UDC Tested <br />2" above piping <br />Does turbine shut down when <br />UDC sensor detects liquid (both <br />product and water)?* <br />[3 Yes ❑ No ® NA <br />Turbine shutdown response time <br />N/A <br />Is system programmed for fail- <br />safe shutdown?` <br />❑ yes ❑ No ® NA <br />Was fail-safe verified to be <br />operational?* <br />❑ yes ❑ No ® NA <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test <br />30 minutes <br />Test Start Time: <br />10:25 am <br />Initial Reading (R,): <br />0.6618 <br />Test End Time: <br />10:40 am <br />Final Reading (RF): <br />0.6621 <br />Test Duration: <br />15 min. <br />Change in Reading (RF-Rj): <br />O.0003 <br />Pass/Fail Threshold or Criteria: <br />+/- 0.002" <br />Test Result: <br />1@ Pass © Fail <br />Was sensor removed for testing? <br />❑ Yes ❑ No ® NA <br />Was sensor properly replaced and ®Yes ❑ No SNA <br />verified functional after testing? <br />Comments — (include frrfarmation on repairs made prior to testing, and recommended follow-up far failed tests) <br />t If the entire depth of the UDC is not tested, specify how much was tested. If the answer to aM of the questions indicated with an <br />asterisk (*) is "NO" or "NA", the entire UDC must be tested.. (See SWRCB .LG -160) <br />