Laserfiche WebLink
. Comments — (include information on repairs made prior to testing, and recommendedfbllqw or ailed tests).. <br />8. SPILL/OVERFILL CONTAINMEN't' BOXES <br />Facility is Not Equipped With Spill/Overfill Containment Boxes 0 <br />Spill/Overfill Containment Boxes are Present, but were Not Tested 0 <br />Test Method Developed By: 0 Spill Bucket Manufacturer <br />0 Other (Specify) <br />ID Industry Standard 0 Professional Engineer <br />Test Method Used: <br />C) Pressure <br />C] Other (5pecify) <br />0 Vacuum 0 Hydrostatic <br />Test Equipment Used: Incon Sump Tester <br />Fill Spill Box # 87 <br />Equipment Resolution: +/-0.002" <br />Fill Spill Box N 91 Fill Spill Box # Diesel <br />Bucket Diameter: <br />12" <br />12" <br />12" <br />Bucket Depth: <br />101, <br />101, <br />101, <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />10 min, <br />10 min. <br />10 min. <br />Test Start Time: <br />10:43 am <br />10:43 am <br />10:43 am <br />Initial Reading (Rj): <br />4.3940 <br />11086 <br />4.5425 <br />Test End Time: <br />10:58 am <br />10:58 am <br />10:58 am <br />Final Reading (Rr): <br />4.3935 <br />11095 <br />4,5424 <br />Test Duration: <br />15 min. <br />15 min. <br />15 min. <br />Change in Reading (RF -RI): <br />0.0005 <br />0.0001 <br />0.0001 <br />Pass/Fail Threshold or <br />Criteria: <br />Test Result: <br />+/-0.002" <br />Pass 0 Fail —rRI <br />+/-0.002" <br />Pass 0 Fail <br />+/-0.002" <br />0 Pass 0 Fail <br />. Comments — (include information on repairs made prior to testing, and recommendedfbllqw or ailed tests).. <br />