—Facility —is Not Equipped With Spill/Overfill Containment Boxes 0 <br />Spill/Overfill Containment Boxes are Present, but were Not Tested 0 <br />Test Method Developed By: ❑ Spill Bucket Manufacturer Industry Standard 0 Professional Engineer <br />0 Other (Specify) <br />Test Method Used: El Pressure El Vacuum 0 Hydrostatic <br />El Other (,5pecify) <br />Test Equipment Used: Incon Sump Tester Equipment Resolution: +/-0.002" <br />NEM5 Vapor Spill Box # 87 <br />Vapor Spill Box N 91 <br />Bucket Diameter: <br />12" <br />129' <br />Bucket Depth: <br />10$1 <br />101, <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />10 min. <br />10 min. <br />Test Start Time: <br />11:05 am <br />11:05 am <br />Initial Reading (Rj): <br />4.2457 <br />3.3401 <br />Test End Time: <br />11:21 am <br />11:21 am <br />Final Reading (RF): <br />4.2455 <br />3.3390 <br />Test Duration: <br />16 min. <br />16 min, <br />Change in Reading (RF-Rj): <br />0,0002 <br />0,0011 <br />Pass/Fail Threshold or <br />Criteria: <br />+/-0.002" <br />+/-0.002" <br />Test Result: <br />IKI Pass ©Fail <br />l Pass 0 Fail <br />Comments — (include information on repairs made prior to testing, and recomnlende4Lo low-upforfailed tests) <br />