Laserfiche WebLink
11/18/2008 10:31 9163731173 WALTONENGINEERING PAGE 05 <br /> STEP i Identify the damaged TO fitting and determine the leak <br /> point.If the leak is at the housing flange, loosen the nut andj <br /> reapply a bead of BOOM HOOFS between the sump wall and <br /> the nut Reinstall the nut. <br /> STEP Z Using a knife, cut the damaged boot along the edge of the <br /> lower clamp.Remove the outer clamp and the insert from the <br /> old finking. <br /> i <br /> 'i <br /> i <br /> W ' <br /> STEP 3 Remove the cut portion of the boot and the old insert <br /> carefully from the pipe and discard. f ' <br /> • I <br /> STEP 4 Install the split corrugated dans stop around the pipe. <br /> i <br /> STEP 5 Push the corrugated dam stop up into the corrugated pipe <br /> until it snaps into the first rib of the corrugated piping.This t� <br /> will prevent the fill compound from filling the corrugated <br /> pipe cavity during the filling stage. ' <br /> S'i`1P 6 Install the TO repair boot Around the pipe and apply a <br /> liberal bead of Blue Seal Glue along both edges of the seas,. <br /> Plush the seam together lightly or clamp lightly until the seam <br /> is cured. (Shue ,Seal Clue typically will cure enough to hold <br /> the fitting together within.five minutes and fully cures within <br /> 40 minutes.':.'. <br /> 4 <br /> - <br /> r'S' <br />