Laserfiche WebLink
JUN-16-2010 09'11 Service Station Systems 408 938 8888 P'11 <br /> 11. SPILL/OVERFILL <br /> NT BOXES <br /> Facility is Not Equipped With Spill/Overfill Containment Boxes 0 <br /> Spill/Overfill Containment Boxes are Present,but were Not Tested El <br /> Test Method Developed By; 0 Spill Bucket Manufacturer 19 In5ustry Standard [I Prof4sional Engineer <br /> [I Other(Spccify) <br /> Test Method Used: []Pressure E3 Vacuum 0 Hydrostatic <br /> Test Equipment Used: Incon Sump Tester pment Resolution: +/-0.002" <br /> 3pill Box#87 Vapor Spill Box#89 Vapor Spill Box 91 <br /> Bucket Diameter: 12" 12" 12" <br /> Bucket Depth: 10" 101t 1011 <br /> Wait time between applying <br /> pressure/vacuuni/water and 10 min. 10 min, 10 min. <br /> starting test: <br /> Test Start Time: 9:33 am 9:56 am 9:06 am <br /> initial Readhig(Rj): 6.0296 5,8438 7.5327 <br /> Final Reading(k-): 6.0299 5.8428 7.5323 <br /> Test Duration: 15 min. 16 min. 15 min. <br /> Change in Reading(RF-Rj): +0.0003 -0,0010 -0,0004 <br /> Test Result: 91 Pass 0 Fail IM Pass 0 Fail 0 Pass 0 Fail <br /> Comments—(include information ov rq�pairs made prior to testing,and recommendedfollow-up:LoLLc�ilcd�tests)�.. <br /> � <br /> TOTAL P'11 <br />