Laserfiche WebLink
JUN-16-2010 09:11 Service Station Systems 408 938 8888 P.10 <br /> s r <br /> 10. SPILL/OVERFILL CONTAINMENT BOXES <br /> Facility is Not Equipped With Spill/Overfill Containment Boxes ❑ <br /> Spill/Overfill Containment Boxes are Present,but were Not Tested ❑ <br /> Test Method Developed By: ❑ Spill Bucket Manufacturer M Industry Standard E] Professional Engineer <br /> ❑Other(Spec) <br /> Kest Method Used: Q Pressure ❑Vacuum ®Hydrostatic <br /> ❑Other(Spec) <br /> Test Equipment Used: Incon Sump Tester Equipment Resolution: +/-0.002" <br /> y L <br /> Fill Spill Box#87 Fill Spill Box#89 Fill Spill Box# 91 pill Spill Sox# Diesel <br /> Bucket Diameter: 12" 12" 12" 1201 <br /> Bucket Depth: I W 10" 10" 10" <br /> Wait time between applying <br /> pressure/vacuum/water and 10 min. 10 min. 10 min. 10 min, <br /> starting test: <br /> Test Start Time: 9:33 am 9:56 am 9:06 am 9:06 am <br /> Initial Reading(R,): 7.4592 5.9182 6.0320 5.2689 <br /> Test End Time: 9:48 am 10:12 am 9:21 am 9:21 am <br /> Final Reading(Rp): 7.4593 5.9176 6.0317 5.2684 <br /> Test Duration: 15 min. 16 min. 15 min. 15 min. <br /> Change in heading(RF-R,): 4-0.0001 .0.0006 -0.0003 -0.0005 <br /> Pass/Fail Threshold or +/-0.002" +/-0.002" +/✓0.002" +/.-0.002" <br /> Criteria: <br /> Test Result: ® Pass Cl Fail ® Pass 0 Fail 0 Paso ❑Fail lad Pass a Fail <br /> Comments—(include information vu repairs made Lrior to testing, and recommended ollow-u foi•failed tests) <br />