Laserfiche WebLink
11 <br />Results of Specificity Testing i <br />Liquid -Phase i Model ` i <br />Test Product : <br />Detector Response: <br />Commercial Gasoline <br />Activated <br />Diesel Fuel <br />Activated <br />Jet -A Fuel <br />Activated <br />JP -4 Jet Fuel <br />Activated <br />n -Hexane <br />Activated <br />Synthetic Gasoline <br />Activated <br />Toluene <br />Activated <br />Xylene(s) <br />Activated <br />The lower detection limit for the four -inch liquid probe was found to lie <br />between 032 cm and 0.16 cm for all of the hydrocarbon test liquids. Lower detection <br />limit results for this detector are summarized in Table 7. <br />Results of Lower Detection Limit Testing for <br />Liquid -Phase Leak Detector Model FD241R <br />Test Product <br />LDL- Thickness (cm) <br />LDL Thickness (cm) <br />Commercial Gasoline <br />0.16 <br />0.32 <br />synthetic Gasoline <br />0.16 <br />032 <br />JP -4 Jet Fuel <br />0.16 <br />032 <br />M <br />