4-0 ATG Leak Test MJR (In -Tank) <br />(Cont.) <br />time and date of the report; the tank number or group <br />number; product grade; LEAK TEST ON; level in <br />inches; gross gallons; net gallons; water level; and <br />temperature at the time of this report. When the Leak <br />Test is terminated, a Leak Test Disable Report will be <br />printed. This printed report will show: your station ID <br />number; time and date of this report; the tank or group <br />number under test; product grade; LEAK TEST OFF; <br />LEAK TEST ENDED; level in inches; gross gallons; <br />net gallons; temperature; water level; duration of test; <br />level change; temperature change and leak rate. This <br />Leak Test Disable Report will also include messages <br />stating the termination method and the results of the .2 <br />gallon per hour Leak Test. Listed on pages 15 and 16 <br />are the possible printed messages and their <br />descriptions. <br />NOTE: Tanks should not be exhumed solely on the <br />basis of leak check information. <br />Figure 5 <br />-rEAR-TESTITEITADS9 <br />REPORT <br />ID # 4701 <br />16:40:02 03115/91 <br />TANK I <br />PRODUCT GRADE SUL <br />A CONCLUSIVE LEAK <br />TEST FOR THIS TANK <br />HAS NOT YET BEEN <br />PERFORMED THIS MONTH <br />YOU MUST PROVIDE <br />ADEQUATE DOWN TIME IN <br />THE NEXT 05 DAYS TO <br />ALLOW A TEST TO RUN <br />END OF REPORT (-005R) <br />cl <br />LEAK TEST REMINDER <br />REPORT <br />ID # 4701 1 <br />16:40:02 03/16/91 <br />TANK I <br />PRODUCT GRADE SUL <br />A CONCLUSIVE LEAK <br />TEST AT REQUIRED % OF <br />CAPACITY HAS NOT YET <br />BEEN PERFORMED ON <br />THIS TANK THIS YEAR <br />YOU MUST PROVIDE <br />ADEQUATE DOWN TIME IN <br />THE NEXT 15 DAYS TO <br />ALLOW A TEST TO RUN <br />END OF REPORT (-005R) <br />