Laserfiche WebLink
SWRCB, January 2002 0 <br />4. TANK ANNULAR TESTING <br />Test Method Developed By: 0 Tank Manufacturer El Industry Standard 0 Professional Engineer <br />n other (Specify) <br />Test Method Uses: 0 Pressure §1 Vacuum 0 Hydrostatic <br />0 Other (Specify) <br />Test Equipment Used: 0 tO 30 in. Hg. Glycerin Filled Vacuum G Equipment Resolution: 0.2 Hg. <br />Is tank Exempt From Testing ?, <br />Tank # I <br />Tank # <br />Tank # <br />Tank # <br />NO <br />Tank Capacity: <br />6,000 gal. <br />Tank Material: <br />Steel & FiLvIrlass <br />Tank Manufacturer: <br />JOOR MANUFACTURING <br />Product Stored: <br />DIESEL <br />Wait time between applying <br />pressure/vacuum/water and starting <br />test: <br />I HR. <br />Test Start Time: <br />8:30 A.M. <br />Initial Reading (Ri): <br />10 in. Hg. <br />Test End Time: <br />10:30 A.M. <br />Final Reading (Rf): <br />10 in. Hg. <br />Test Duration: <br />2 FIRS. <br />Change in Reading (Rf-Ri): <br />0 <br />Pass/Fail Threshold or Criteria: <br />0.002 <br />Test Result: <br />PASS <br />Was sensor removed for testing? <br />YES <br />Was sensor properly replaced and <br />verified functional after testing? <br />YES <br />Comments - (include information on repairs made prior to testing, and recommendedfollow-upforfailed tests) <br />I Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br />containment, such as systems that are hydrostatically monitored or under constant vacuum, are exempt from periodic containment <br />testing. lCalifornia Code of Regulations, Title 23, Section 2637(a)(6)) <br />Revision: <br />