Laserfiche WebLink
I <br />SWRCB, January 2002 <br />Facility is Not Equipped With Spill/Overfill Containment Boxes 11 <br />Spill/Overfill Containment Boxes are Present, but were Not Tested n <br />Test Method Developed By: <br />Spill Bucket Manufacturer <br />0 Other (Specify) <br />0 Industry Standard 0 Professional Engineer <br />Test Method Uses: <br />El Pressure <br />0 Other (Specify) <br />❑ Vacuum Hydrostatic <br />Egui2ment Used: Incon TS -STS Sump Testing §ystern <br />Equipment Resolution: 0.002 in. <br />—Test <br />Spill Box# Fill Spill Box # <br />Spill Box # Spill Box # <br />Bucket Diameter: <br />12" <br />Bucket Depth: <br />loff <br />Wait time between applying <br />pressure/vacuum/water and <br />test: <br />30 MIN. <br />—starting <br />Test Start Time: <br />9:15 A.M. <br />Reading (Ri): <br />3.8493 IN. <br />—Initial <br />Test End Time: <br />9:30 A.M. <br />Final Reading (Rf): <br />3.8487 IN. <br />Test Duration: <br />2xI5 min. <br />Change in Reading (RF-Ri: <br />-0.0006 IN. <br />Pass/Fail Threshold or Criteria: <br />0.002 in. <br />Test Result: <br />IPASS <br />I <br />I <br />Comments - (include information on repairs made prior to testing, and recommendedfollow-upforfaded tests) <br />Please direct any comments regarding this form to: <br />SWRCB UST Program, Attn: Scott Bacon <br />1001 "1" Street, Box 944212 <br />Sacramento, CA 95814 <br />Phone: (916) 341-5873, Fax: (916) 341-5808 <br />e-mail: baconsOdcwl2.'swrcb.ca.gov <br />