Laserfiche WebLink
4cy1E- �"!Viffo <br /> 7 In-Tank Setup n r'T 6) 94iruct <br /> ENVIRONMENTAL HEALTH <br /> High Product DEPARTMENT <br /> If necessary,press STEP until you see the message: <br /> T1:(Product Label) <br /> HIGH PRODUCT:000% <br /> High Product warns when the volume of fluid in the tank exceeds the value you enter here.The High Product alarm <br /> occurs whenever this value is exceeded,whether or not a delivery is in progress. <br /> In U.S.installations this is especially useful in applications such as used oil holding tanks,where the rate of fill can <br /> be too gradual for the system to recognize the increase as a delivery and activate the Overfill Limit.It can trigger <br /> the same alarm indications as Overfill Limit.Set this limit at a percentage that is between the Overfill Limit <br /> percentage and 95% (of the tank's capacity) [see Figure 7-11. <br /> In international installations,this is especially useful to warn of an impending overfill. It can trigger the same alarm <br /> indications as Overfill Limit Set this limit to 989b if the label volume is greater than 25,000 litres and to 96%if the <br /> label volume is less than 25,000 litres. <br /> Press CHANGE.Enter the percent limit.Press ENTER to confirm your entry.The system displays: <br /> HIGH PRODUCT.XX*/. <br /> PRESS<STEP>TO CONTINUE <br /> Delivery Limit <br /> If necessary,press STEP until you see the message: <br /> IT1:(Product Label) <br /> DELIVERY LIMIT.000% <br /> Delivery Limit warns when the level of fluid in the tank drops to a level at which the operator calls for a delivery.Set <br /> this percentage at a volume higher than that of the Low Product alarm[see Figure 7-1]. <br /> Press CHANGE.Enter the percent limit.Press ENTER to confirm your entry.The system displays, <br /> DELIVERY LIMIT:XX% <br /> PRESS 2>TO CONTINUE <br /> Low Product <br /> If necessary,press STEP until you see the message: <br /> ITi:(Product Label) <br /> LOW PRODUCT:000000 <br /> Low Product warns when volume in a tank recedes to the level you enter here[see Figure 7-11, <br /> In international installations,assuming no water in the tank,this limit should be set no lower than:the tank volume <br /> at 250 mm for Mag probe types 8473,or the tank volume at 125 mm for Mag probe types 8498(these are the <br /> minimum volumes that can be measured by each probe type). <br /> Press CHANGE. Enter the volume. Press ENTER to confirm your entry.The system displays: <br /> LO PRODUCT:XXXXXX <br /> LOUD <br /> <STEP>TO CONTINUE <br /> 7-17 <br />