Laserfiche WebLink
UNDER DISP94SER CONTAINMENT DC TESTING <br /> Test Method By: O Manufacturer 0 Industry Standard o Professional Engr o Other(see below) <br /> Test Method Uses: O Pressure O vacuum • Hydrostatic o Other(see below) <br /> Measuring Equipment Used: INCON TS-STS (Electronic Sump Test System) <br /> Description Disp#1/2 Disp#3/4 Disp#5/6 <br /> UDC manufacturer Bravo Bravo Bravo <br /> UDC material Steel Steel Steel <br /> UDC depth (inches) 9" 9" 9" <br /> Height from UDC bottom to highest Bottom Bottom Bottom <br /> piping penetration <br /> Height from UDC bottom to lowest Bottom Bottom Bottom <br /> electrical penetration <br /> Condition of UDC prior to testing Dry Dry Dry <br /> Portion of UDC tested Entire Entire Entire <br /> Type of shut-down present Float Float Float <br /> Was sensor removed for testing? N/A N/A N/A <br /> Was sensor properly replaced after testing? N/A N/A N/A <br /> Depth of water level from UDC bottom (in.) 8" 8" 8" <br /> Wait time for water level to stabilize (hr:min) 0:15 0:12 0:08 <br /> Test start time 11:56 AM 10:10 AM 10:45 AM <br /> Initial Probe Reading 0.3944 0.7354 1.5222 <br /> Test end time 12:11 PM 10:25 AM 11:00 AM <br /> Final Probe Reading 0.3944 0.7352 1.5221 <br /> Test duration (hr:min) 0:15 0:15 0:15 <br /> Change in water level (±0.0000 inches) 0.0000 -0.0002 -0.0001 <br /> Pass/Fail threshold (±0.0020 inches Hr.) 0.0020 0.0020 0.0020 <br /> TEST RESULT PASS PASS PASS <br /> Comments: <br /> © 2004 Walton Engineering,Inc. <br />