Laserfiche WebLink
• <br />SWRCB, January 2002 Page 7 of 7 <br />9. SPILL/OVERFILL CONTAINMENT BOXES <br />Facility is Not Equipped With Spill/Overfill Containment Boxes [ <br />Spill/Overfill Containment Boxes are Present, but were Not Tested <br />Test Method Developed By: <br />[ Spill Bucket Manufacturer <br />[Other (speciify) <br />N Industry Standard [ Professional Engineer <br />Test Method Uses: <br />[Pressure <br />[Other (spec) <br />[ Vacuum 11 Hydrostatic <br />ui ent Used: INCON TS - STS <br />Bog # Fill bucket Spill Box # <br />w <br />Bucket Diameter: 12" <br />Equipment Resolution: 0.001 <br />Spill Box # Spill Bot # <br />Bucket Depth: <br />12" <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />30 Min <br />Test Start Time: <br />9:25 AM/ 9:42 AM <br />Initial Reading (Rt): <br />7.2114" / 7.2113" <br />Test End Time: <br />9:40 AM 19:57 AM <br />Final Reading (RF): <br />7.2108" / 7.2111 <br />Test Duration: <br />2 X 15 Minutes <br />Change in Reading (RF -RD: <br />-0.0002 <br />Pass/Fail Threshold or Criteria: <br />0.001" <br />Comments - (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />Please direct any comments regarding this form to: <br />SWRCB UST Program, Attn: Scott Bacon <br />1001 "I" Street, Box 944212 <br />Sacramento, CA 95814 <br />Phone: (916) 341-5873, Fax: (916) 341-5808 <br />e-mail: bacons@cwp.swrcb.ca.gov <br />Revision: <br />