Laserfiche WebLink
! SWRCB,January 2002 0 0 Page 2 of 5 <br /> 4. TANK ANNULAR TESTING <br /> Test Method Developed By: Industry Standard Test Method Used: Vacuum <br /> Test Equipment Used: Vacuum Gage 0"Hg —20"Hg Equipment Resolution: +/- 0.5"Hg <br /> Red Dye Diesel Tank <br /> Tank Exempt From Test?' ❑Yes ®No <br /> Tank Capacity, 550 gallons <br /> Tank Material: Fiberglas <br /> Tank Manufacturer: Xerxes <br /> Product Stored: Red Dye Diesel <br /> Wait after applying vacuum & test: 15 minutes <br /> Test Start Time: 2:45 PM <br /> Initial Reading (RI): -10" H <br /> Test End Time: 3:45 PM <br /> Final Reading (RF): -10" H <br /> Test Duration: 1 hour <br /> Reading Change(RF-RI): 0 <br /> Pass/Fail Criteria: +/- 0" H <br /> Test Result: ®Pass []Fail <br /> Sensor removed for test? ❑Yes ❑No DNA <br /> Sensor replaced and verified functional? ❑Yes ❑No DNA <br /> Comments—(include information on repairs made prior to test, and recommended follow-up for failed tests) <br /> ' Secondary containment systems where the continuous monitoring automatically monitors both the primary and <br /> secondary containment, such as systems that are hydrostatically monitored or under constant vacuum, are exempt from <br /> periodic containment testing. {California Code of Regulations, Title 23, Section 2637(a)(6)1 <br />