Laserfiche WebLink
SWRCB, January 2002 <br />Test Method Developed By: <br />�._ `�� Pagett J of <br />4. TANK ANNULAR TESTING <br />X Tank Manufacturer ❑ Industry Standard ❑ Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: <br />❑ Pressure X Vacuum ❑ Hydrostatic <br />❑ Other (Spec) <br />Test Equipment Used: Gast Vacuum Pump/Vacuum Gauges in Hg. Equipment Resolution: -'/�" x -30 Hg. <br />Tank # 1 Tank # Tank # Tank # <br />Is Tank Exempt From Testing?' ❑ Yes x No ❑ Yes No ❑ Yes ❑ No ❑ Yes ❑ No <br />Tank Capacity: <br />IOK <br />Tank Material: <br />Jacketed Double <br />Wall Steel <br />Tank Manufacturer: <br />K&T Steel <br />Product Stored: <br />Dyed Diesel <br />Wait time between applying <br />vacuum and starting test: <br />15 Minutes <br />Test Start Time: <br />9:50 <br />Initial Reading (RI): <br />-5 Hg. <br />Test End Time. <br />10:50 <br />Final Reading (RF): <br />-5 Hg. <br />Test Duration: <br />1 Hour <br />Change in Reading (RF -R,): <br />0 Hg. <br />Pass/Fail Threshold or Criteria: <br />No loss in Hg. <br />Test Result: <br />Pass <br />Was sensor removed for testing? <br />Yes <br />Was sensor properly replaced and yes <br />verified functional after testing? <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />Annular Vent to Atmosphere capped for Test. <br />' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br />containment, such as systems that are hydrostatically monitored or under constant vacuum, are exempt from periodic containment <br />testing. {California Code of Regulations, Title 23, Section 2637(a)(6)} <br />