Laserfiche WebLink
V �~ <br /> Scope <br /> This procedure will provide a Veeder-Root ATG certified technician a procedure to safely test tank overfill <br /> protection. <br /> Reference Documents <br /> ° V*ederRootTLS'3XXOperators Manual (57G013'G10) <br /> ° Voeder-RuotTLG'8%XSetup Manual (578O13'O23) <br /> ~ VaederRootTL8'45USetup and Operation Screens Manual (577O13'048) <br /> ^ Veeder-RootTLS'45OPLUS/TLS4Operator's Manual (577014'11O) <br /> ~ VeederRootTLS4Quick Start(577Q14'084) <br /> , VeederRootOverfill Alarm Installation Guide(O7OO13'58D) <br /> Consoles <br /> TLS'45OPLU9.TLB4n.TLS4i.TLB'45Oand TL88XX <br /> Requirements <br /> TLS'45OPLUS.TLS4c.TLS4i.TLS'45O:Automatic Event:Device Task programmed totrigger onTank Overfill and <br /> close arelay feeding voltage tothe Overfill alarm device. <br /> TLS-3XX:Output relay programmed to close a relay on a Tank Overfill alarm feeding voltage to the Overfill alarm <br /> device. <br /> Testing Procedure <br /> 1. Inspection <br /> u. Verify the levels in the tank to make sure there is product in the tank and that the tank is enabled. <br /> b. If the site is currently receiving a delivery,wait until the delivery is complete. <br /> c. |fthe tank inperforming uGLDtank test,stop the test. <br /> 2. Pnmpesdkon <br /> a. Turn Alarm filtering off,as this will allow you toclear alarms quicker. Refer tuTLG'3%XSetup manual <br /> (57GD13'GO3)orTLS4XXon-line help. <br /> b. Program Delivery delay to 1 minute,this will allow the delivery to be completed quicker. <br /> 1. Note the customers original value,ooyou can restore dafter the test. <br /> 24 <br />