Laserfiche WebLink
, ., .1 0 Page of <br />Test Method Developed By: <br />❑ Sump Manufacturer X Industry Standard <br />❑ Other (Specify) <br />❑ Professional Engineer <br />Test Method Uses: <br />❑ Pressure ❑ Vacuum <br />❑ Other (Spec) <br />X Hydrostatic <br />Measuring Equipment Used for Testing: INCON TS -STS V2.1 <br />Fill Sump # D Fill Fill Sump # <br />Sump Diameter: 12" <br />Fill Sump # <br />Sump Depth: <br />16" <br />Height from Tank Top to <br />Highest Piping Penetration: <br />0" <br />Height from Tank Top to <br />Lowest Electrical Penetration: <br />N/A <br />Condition of sump prior to <br />testing: <br />Dry <br />Portion of Sump Tested <br />All <br />Sump Material: <br />Plastic <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />15 Min. <br />Test Start Time: <br />12:34 <br />Initial Reading (R4): <br />5.2948 <br />Test End Time: <br />12:49 <br />Final Reading (RF): <br />5.2946 <br />Test Duration: <br />15 Min. <br />Chane in Reading (RF -RI): <br />.0002 <br />Pass/Fail Threshold: <br />.002 <br />Test Result: <br />Pass <br />Is there a sensor in the sump? <br />No <br />Does the sensor alarm when <br />either product or water is <br />detected? <br />N/A <br />Was sensor removed for <br />testing? <br />N/A <br />Was sensor properly replaced <br />after testing? <br />N/A <br />Comments — (include information on repairs made to facilitate a passing test and indicate whether a <br />permit was obtained for the repairs) <br />All hydrostatic test performed twice to insure testinp- results <br />R.C.U.S.T.COM December 2001 <br />