Laserfiche WebLink
r <br />SWREB, January 2002 Page of % <br />4. TANK ANNULAR TESTING <br />Test Method Developed By: X Tank Manufacturer 0 IndustryStandard 0 Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: 0 Pressure X Vacuum 0 Hydrostatic <br />0 Other (Spec) <br />Test Equipment Used: Vacuum Gage Equipment Resolution: .5" Hg <br />Tank # 1 — 87 <br />0 Yes X No <br />�7T'--77 <br />12,000 GallonsC-11000faiml <br />Tank Manufacturer: <br />J0or <br />Product Stored: <br />87 . <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />10 Min. <br />Test Start Time: <br />11:15 <br />Initial Reading (Rr): <br />10" Hg <br />Test End Time: <br />12:15 <br />Final Reading (RF): <br />10" Hg <br />Test Duration: <br />1 Hour <br />Change in Reading (RF -R,): <br />0" Hg <br />Pass/Fail Threshold or Criteria: <br />+/- 0" Hg <br />Test Result: <br />X Pass 0 Fail <br />Was sensor removed for testing? <br />X Yes ❑ No ❑ NA <br />Was sensor properly replaced and <br />verified functional after testing? <br />X Yes 0 No 0 NA <br />Comments — (include information on repairs made prior to testing and recommended follow-up for failed tests) <br />l Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br />containment, such as systems that are hydrostatically monitored or under constant vacuum, are exempt from periodic containment <br />testing. {California Code of Regulations, Titl� 23, Section 2637(a)(6)) <br />i <br />