Laserfiche WebLink
.1 ', <br />SWRCB, January 2002 <br />ANNULAR TESTING <br />Page � of -7 <br />1+. TANK <br />Test Method Developed By: X Tank Manufacturer ❑ Industry Standard ❑ Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: ❑ Pressure X Vacuum ❑ Hydrostatic <br />❑ Other (Spec) <br />Test Equipment Used: Vacuum Gage Equipment Resolution: .5" Hg <br />�i <br />Is Tank Exempt From Testing?' <br />Tank#1-87 <br />❑ Yes X No <br />12,000 Gallons <br />Tank Capacity: <br />Tank Material: <br />Glassteel <br />Joor <br />Tank Manufacturer: <br />Product Stored: <br />87 <br />Wait time between applying <br />pressure/vacuum/water and <br />test: <br />10 Min. <br />startin <br />Test Start Time: <br />11:15 <br />Initial Reading (Rj): <br />10" Hg <br />Test End Time: <br />12:15 <br />Final Reading (RF): <br />10" Hg <br />Test Duration: <br />1 Hour <br />Change in Reading (RF -RI): <br />0" Hg <br />Pass/Fail Threshold or Criteria: <br />+/- 0" Hg <br />Test Result: <br />X Pass ❑ Fail <br />Was sensor removed for testing? <br />X Yes ❑ No [INA <br />NAWas <br />Was sensor properly replaced and <br />verified functional after testin ? <br />- <br />X Yes []No ❑ NA <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br />containment, such as systems that are hydrostatically monitored or under constant vacuum, are exempt from periodic containment <br />testing. {California Code of Regulations, Title 23, Section 2637(a)(6)1 <br />