Laserfiche WebLink
bp <br /> 0 LINE LEAK DETECTOR TEST <br /> Facility #: 5450 Date: 09/01/11 <br /> Address: 1617 W. Fremont <br /> City, State: Stockton, CA <br /> Testing Information <br /> 1 2 3 4 5 <br /> Product: 91 87 <br /> Manufacturer red jacket CPT <br /> Leak Detector Serial Number n/a <br /> Leak Detector Model No. FXIV <br /> Full Operating Pressure (psi): 32 <br /> Test Leak Rate (ml/min)(gph) 3.00 <br /> Bleed Back Rate ( l): 100 <br /> Turbine Holding Pressure (psi): 14 <br /> Metering Pressure (psi): 19 <br /> Open/Trip Time (mechanical only): 3 sec <br /> Pass / Fail pass Not Tested <br /> Comments: 87 CPT LD not tested due to training certification misunderstanding. <br /> Note: Pass = Leak detector reads leak and meters line. <br /> Fail = Leak detector did not read leak. <br /> This letter certifies that the annual leak detector tests were performed at the above referenced facility according to the equipment <br /> manufacturers procedures and limitations and the results as listed are to my knowledge true and correct.The mechanical leak test <br /> detector test pass/fail is determined using a low flow threshold trip rate of 3 gph at 10 PSI. <br /> Inspected By: Contractor FASTECH-Fueling & Services Technologies, Inc. <br /> Technician: Omar Ruiz Lic#: B35686 <br /> Signature: <br />