Laserfiche WebLink
Pi=c. EivL_ n <br /> N n mom= 's�p� 0 W 3;7] <br /> TANK ANNULARTESTING OCT 2 5 2017 <br /> ENVIRONMENTAL HERLQ <br /> Test Method By: • Manufacturer O Industry Standard O Professional Enge. PV t 'below) <br /> Test Method Uses: O Pressure • Vacuum o Hydrostatic o Other(see below) <br /> Measuring Equipment Used: Vacuum Gauge (range 0 to 30 inches Hg) <br /> Description Tank#1 Tank#2 Tank#3 <br /> Product stored Gasoline-87 Gasoline-89 Gasoline-91 <br /> Tank manufacturer Xerxes Xerxes Xerxes <br /> Tank material FRP FRP FRP <br /> Tank capacity (US gallons) 10,000 10,000 8,000 <br /> Is this a multi-compartment tank? No No No <br /> Dry or Brine filled annular? No No No <br /> Monitoring system show normal annular? Yes Yes Yes <br /> Is water table above tank bottom? Unknown Unknown Unknown <br /> Was sensor removed for testing? Yes Yes Yes <br /> Was sensor properly replaced after testing? Yes Yes Yes <br /> Wait time for vacuum to stabilize (hr:min) :10 :10 :10 <br /> Test start time 9:45 AM 9:49 AM 9:52 AM <br /> Initial vacuum (inches Hg) 7.0 7.0 7.0 <br /> Test end time 10:45 AM 10:49 AM 10:52 AM <br /> Final vacuum (inches Hg) 7.0 7.0 7.0 <br /> Test duration (hr:min) 1:00 1:00 1:00 <br /> _change in vacuum (inches Hg) 0.0 0.0 0.0 <br /> Pass/Fail threshold (inches Hg/hour) 2.0 2.0 2.0 <br /> TEST RESULT PASS PASS PASS <br /> Comments: <br /> ©2017 Walton Engineering,Inc. <br />