Laserfiche WebLink
UNDER DISPENSER TI ENT (UDC) TESTING <br /> Test Method By: o Manufacturer • Industry Standard o Professional Engr o Other(see below) <br /> Test Method Uses: o Pressure o vacuum • Hydrostatic o Other(see below) <br /> Measuring Equipment Used: INCON TS-STS (Electronic Sump Test System) <br /> Description Disp#1/2 Disp#3/4 <br /> UDC manufacturer Brovo Brovo w <br /> UDC material Steel Steel <br /> -77 z <br /> UDC depth (inches) 9 9 <br /> Height from UDC bottom to highest Bottom Bottom OCT 2 5 2017 <br /> piping penetration <br /> Height from UDC bottom to lowest Bottom Bottom <br /> electrical penetration ENVIRONMENTAL <br /> VI E AL L <br /> TH <br /> Condition of U DC prior to testing Dry Dry DIPAPTMsem_N- <br /> Portion of UDC tested Entire Entire <br /> Type of shut-down present Floats and chains Floats and chains <br /> Was sensor removed for testing? N/A N/A <br /> Was sensor properly replaced after testing? N/A N/A <br /> Depth of water level from UDC bottom (in.) 6 6 <br /> Wait time for water level to stabilize (hr:min) :15 :15 <br /> Test start time 12:19 PM 12:19 PM <br /> Initial Probe Reading 1.8650 1.5892 <br /> Test end time 12:34 PM 12:34 PM <br /> Final Probe Reading 1.8662 1.5900 <br /> Test duration (hr:min) 0:15 0:15 <br /> Change in water level (±0.0000 inches) 0.0012 0.0008 <br /> Pass/Fail threshold (±0.002 inches/;Hr.) 0.0020 0.0020 <br /> TEST RESULT PASS PASS <br /> Comments: <br /> ©2017 Walton Engineering,Inc. <br />