Laserfiche WebLink
SWRCB,January 2002 Page_of_ <br /> 6. PIPING SUMP TESTING <br /> Test Method Developed By: F1 Sump Manufacturer ❑Industry Standard X Professional Engineer <br /> a Other(Specify) <br /> Test Method Used: a Pressure Q Vacuum X Hydrostatic <br /> n Other(Specify) <br /> Test Equipment Used: Caldwell Level Change Indicator Equipment Resolution: .002 <br /> Sump#1-Diesel Sump#2-Gas Sump# Sump# <br /> Sump Diameter: 48" 48" <br /> Sump Depth: 30" 301* <br /> Sump Material: Fiberglass Fiberglass <br /> Height from Tank Top to Top of 22" 21" <br /> Highest Eij)ing Penetration: <br /> Height from Tank Top to Lowest 18" 18" <br /> Electrical Penetration: <br /> Condition of sump prior to testing: Dry Dry <br /> Portion of Sump Tested' Water Line 26" Water Line 25" <br /> Does turbine shut down when <br /> sump sensor detects liquid(both Suction System Suction System <br /> product and water)?* <br /> Turbine shutdown response time. N/A NIA <br /> Is system programmed for fail-safe N/A N/A <br /> shutdown?* <br /> Was fail-safe verified to be No No <br /> operational?* <br /> Wait time between applying water 5 Minutes 5 Minutes <br /> and starting test: <br /> Test Start Time: 9:32 10:15 <br /> Initial Reading(Rc): .041 .001 <br /> Test End.Time: 10:02 10:45 <br /> Final Reading(RR): .001 .001 <br /> Test Duration: 30 Minutes 30 Minutes <br /> Change in Reading.(R-•Ra): 0 0 <br /> PassfFail Threshold or Criteria: .005/30 Minutes .005/30 Minutes <br /> Test:Ra[t' <br /> Fuss Pam <br /> Was sensor removed for testing? Yes Yes <br /> Was sensor properly replaced and Yes Yes <br /> verified functional after testing? <br /> Comments—(mclude information on repairs made prior to testing,and recommended follow-upforfailed tests) <br /> 'If the entire depth of the sump is not tested,specify how much was tested. If the answer to any of the questions indicated with an <br /> asterisk(*)is`NO"or"NA",the entire sump must be tested. (See SWRCB LG-160) <br />