Laserfiche WebLink
SWRCB,January 2002 Page of <br /> 4. TANK ANNULAR TESTING <br /> Test Method Developed By: X Tank Manufacturer Industry Standard C'Professional Engineer <br /> Other(Spec) <br /> Test Method Used: Pressure X Vacuum Hydrostatic <br /> Other(Spec) <br /> Test Equipment Used: Gast Vacuum Pump/Vacuum Gauge in Hg. Equipment Resolution: - %2"x-30"Hg. <br /> Tank#1 Tank# Tank# Tank# <br /> Is TarExemptrom Testing?' No <br /> Tank 12K <br /> Tank Material: Fiberglass <br /> Tank Manufacturer: Owens Corning <br /> Product Stored: Jet A <br /> Wait time between applying <br /> vacuum and startingtest: 5 Minutes <br /> Test Start Time: 9:30 <br /> Initial Reading(Ri): -10"Hg. <br /> Test End Time: 10:30 <br /> Final Reading(RF): -10"Hg. <br /> Test Duration: 1 Hour <br /> Change in Reading(RF-Ri): 0"Hg. <br /> Pass/Fail Threshold or Criteria: No loss in Hg. <br /> Test Result: Pass <br /> Was sensor removed for testing? No <br /> Was sensor properly replaced and N/A <br /> verified functional after testing? <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> DL ' 1-4 21017 <br /> FENIVIRQNMENT-AL HEALTH <br /> DEPARTMENT <br /> ' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. {California Code of Regulations,Title 23,Section 2637(a)(6)) <br />