Laserfiche WebLink
Waterloo SB989 Repair Work: Permit SR0061062 <br />2S12 Waterloo, Stockton <br />91/DSL Annular Space Pass <br />DSL Piping Pass <br />91 Turb Sump Pass <br />87 Piping Failed, both entries are cracked and need shallow entry repairs. Same repair as existing subittal <br />91 Piping UDC 1/2 91 entry is unrepairable without breaking concrete. Existing repair by others is not certified. <br />Item Status <br />UDC 3/4 87 Entry Boot Requires Diversified shollow repair. Same as existing permit submittal from Diversified <br />UDC 1/2 87 Entry Boot Requires Diversified shollow repair. Same as existing permit submittal from Diversified <br />91 Entry Boot Requires Diversified shollow repair. Same as existing permit submittal from Diversified <br />Recommended Repair: <br />1. Break concrete on north side of 1/2 <br />2. Removed existing repair and clean top and bottom of UDC <br />3. Install new Shallow Repair Kit for Total Containment <br />4. Install stainless bolts and nuts to secure entry to UDC <br />5. Back fill and inspect <br />Ll <br />ft— <br />Repair by others <br />