Laserfiche WebLink
JUN -04-2008 14:44 Service Station Systems 408 938 8888 P.06 <br />0 is <br />Test Method Developed By. <br />❑ Piping Manufacturer ® Industry Standard ❑ Professional Engineer <br />❑ Other (Specify) <br />Test Method Used: <br />® Pressure <br />❑ Other (Specify) <br />❑'Vacuum <br />❑ Hydrostatic <br />Test Equipment Used: Test reducer boots, Nitrogen and gauges <br />Piping Run # 87 B )Wiping Run # 89 B <br />Equipment Resolution: 0.5% of span <br />Piping Run # 91 B <br />Piping Material: <br />Fiberglass <br />Fiberglass <br />)Fiberglass <br />Fiping Manufacturer. <br />Ameron <br />Ameron <br />Ameron <br />Piping Diameter: <br />3" <br />3" <br />3.. <br />Length of Piping Run: <br />150' <br />150' <br />150' <br />Product Stored: <br />Gasoline <br />Gasoline <br />Gasoline <br />Method and location of <br />i in -run isolation: <br />Reducer BooWnettingg <br />Reducer Bootsffitfingg <br />Reducer BooUffittingg <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />10 minutes <br />10 minutes <br />10 minutes <br />Test Start Time: <br />8:30 am <br />8:30 am <br />8:30 am <br />Initial Reading (RO: <br />5 psi <br />5 psi <br />5 ,psi <br />Test End Time: <br />9:30 am <br />9:30 am <br />9:30 am <br />Final Reading (RF): <br />5 psi <br />5 psi <br />5 psi <br />Test Duration: <br />1 hour <br />1 hour <br />1 hour <br />Change in Reading (RF -RI): <br />None <br />None <br />None <br />Pass/Fail Threshold or <br />Criteria: <br />No detectable loss <br />No detectable loss <br />No detectable loss <br />Test Results <br />® Paas Fail <br />o Pass Fail <br />® Pass Fail <br />COl{IlmentS — (include infomiation on repairs made prior to testing, and recommended follow-up forafailed tests) <br />