JUN -04-2008 14:50 Service Station Systems 408 938 8888 P.19/19 <br />0 0 <br />Facility is Not Equi ped With Spill/overfill Containment Boxes p <br />Spill/Overfill Containment Boxes are Present, but. were Not Tested El <br />Test Method Developed By: <br />❑ Spill Bucket Manufacturer ® Industry Standard ❑ Professional Engineer <br />❑ Other (Specify) <br />Test Method Used: <br />® Pressure <br />Q Other (Specify) <br />p Vacuum 0 Hydrostatic <br />Test Equipment Used: Incon Sump Tester <br />>Fill Spill Box # 89 <br />/ <br />Equipment Resolution: +/-0.0002" <br />Vapor Spill Box # 87 <br />Bucket Diameter: <br />12" <br />12" <br />Bucket Depth: <br />10" <br />10" <br />Wait time between applying <br />pressure/vacuum/water and <br />startin test; <br />10.min. <br />10 min. <br />Test Start Time: <br />8:48 am <br />8:48 am <br />Initial Reading (Rt): <br />4.5066 <br />5.7310 <br />Test End Time: <br />9:04 am <br />9:04 am <br />Final Reading (RF): <br />4.5065 <br />5.7310 <br />Test Duration: <br />16 min. <br />16 min. <br />Change in Reading (RF -lam: <br />-0.0001 <br />None <br />PassMail Threshold or <br />Criteria: <br />+/-0.002" <br />+/-0.002" <br />Test Result: <br />® Pass Fail <br />El Pass Fail <br />Comments — (include infors w ion on repairs made prior to testing, and recommended follow-up for failed tests) <br />Tightened swivel adapter on 87 vapor bucket <br />Tighted drain on 89 fill bucket <br />TOTAL P.19 <br />