Laserfiche WebLink
SWRCB,January 2002 0 0 Page_�o of tA 3 <br /> 16. UNDER-DISPENSER CONTAPMENT(UIDC)TESMG <br /> Test Method Developed By: 01 Manufacturer 0 industry Standard X Professional Engineer <br /> 0 Other(Specify) <br /> Test Method Used: 11 Pressure 11 Vacuum X Hydrostatic <br /> 0 Other(Specift) <br /> Test Equipment Used: MTS Mag Probe W/TDU Meter Equipment Resolution: .001" <br /> 14-Satellite UIDC#17/18 UDC#16-Saftelite UDC#18-Sate flite <br /> UDC Manufacturer: Owens Coming Owens Cornin Owens Corrupp, Owens Co <br /> UDC Material: Fiberglass Fiberglass Fiberglass Fiberalass <br /> UDC Depth: 26" 26" 26" 265 <br /> Height from UDC Bottom to Top V 12" 123' 12" <br /> of H!y <br /> hest Pi in Penetration: <br /> Height from UDC Bottom to 77' 6" 6" 6" <br /> Lowest Electrical Penetration: <br /> Condition of UDC prior to Good Good Good Good <br /> testing: <br /> Portion of UDCTested 149' 14" 14" 14" <br /> Does turbine shut down when <br /> UDC sensor detects liquid(both 0 Yes X No El NA 0 Yes XNo DNA DYes XNo 11 NA 0 Yes X No DNA <br /> product and water)?* <br /> Turbine shutdown re!ponse time N/A N/A N/A NA <br /> Is system programmed for fail- 0 Yes 0 No X NA 0 Yes DNo XNA DYes 0 No X NA 0 Yes Cl No X NA <br /> safe shutdown?' <br /> Was fail-safe verified to be 0 Yes 0 No X NA D Yes 0 No XNA D Yes 0 No X NA 0 Yes DNo XNA <br /> _2perational?' <br /> Wait time between applying <br /> pressure/vacuum/water and 10 in 10 in 10 in 10 in <br /> starting test <br /> Test Start Time: 15:15 15:15 14:50 14:50 <br /> Initial Reading(Rj): 0.0001, 0.0001, 00WI, 0,0001, <br /> Test End Time: 15:27 15:27 15:02 15:02 <br /> Final Reading(RF): 0.000" 0.0w 0 - 0. 0" <br /> Test Duration: 12 Min 12 in 12 in 12 in <br /> Change in Rea F-Ri): 0.0001, 0.0001, 0AM11 0. 0" <br /> Pass/Fail Threshold or Criteria: +/-.002" +/-.002" +/-,002" +/-.002" <br /> T' "t R"ot; X Pus 0P <br /> FOR ' 'X P Faw x Pus 0 Fall, <br /> , W -- - <br /> Was sensor removed for testing? X Yes 0 No 0 NA X Yes 0 No 0 NA X Yes 0 No 0 NA X Yes 0 No 0 NA <br /> Was sensor properly replaced and X Yes DNo DNA X Yes 0 No 0NArXYes DNo DNA X Yes 0 No D NA <br /> verified functional after testin ? I <br /> Comments—(include information on repairs madeEpr[io2r�tirt , aazd recommen4Ldfoojl - �fafled ailed <br /> If the entire depth of the UDC is not tested,specify how much was tested. If the answer to My of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire UDC must be tested. (See SB LG-160) <br />