Laserfiche WebLink
SWRCB,January 2002 0 0 Page_13 of 443 <br /> 19. UNDER-DISPENSER CONTAINMENT QTQ TESMG <br /> Test Method Developed By: El UDC Manufacturer 0 industry Standard X Professional Engineer <br /> 0 Other(Specify) <br /> Test Method Used: 0 Pressure 0 Vacuum X Hydrostatic <br /> 0 Other(Specify) <br /> Test Equipment Used: NITS Mag Probe W/TDU Meter Equipment Resolution: .001" <br /> UDC#1/2 UDC#3/4 UDC#5/6 UDC#7/8 <br /> UDC Manufacturer: Owens C Owens Cornixn% Owens Coming Owens Corrin lass <br /> 26 <br /> UDC Material: Fibggl mi 7 glass giber Fi"r ass <br /> ass Fiber <br /> UDC Depth: 26" 26'5 26" 26" <br /> �7 77 <br /> Height from UDC Bottom to Top 12" 1291 12" 12" <br /> of Hi est Piping Penetration: <br /> Height from UDC Bottom to 6'9 6'9 T' <br /> Lowest Electrical Penetration: <br /> Condition of UDC prior to Good Good Good Good <br /> testing: _—F— <br /> Portion of UDC Tested 1411 14" 14" 14" <br /> Does turbine shut down when <br /> UDC sensor detects liquid(both D Yes X No 0 NA 0 Yes X No DNA 0 Yes X No 0 NA 0 Yes XNo DNA <br /> redact d ter?s <br /> Turbine shutdown response time N/A N/A N/A N/A <br /> Is system programmed for fail- D Yes XNo 0 NA D Yes X No D NA 0 Yes X No 0 NA 0 Yes XNo DNA <br /> safe shutdown?* <br /> Was fail-safe verified to be 0 Yes XNo 0 NA D Yes X No D NA D Yes XNo D NA 0 Yes XNo D NA <br /> o rational?* <br /> Wait time between applying <br /> pressure/vacuum/water and 10 in 10 in 10 in 10 in <br /> starkin test <br /> Test Start Time: 17:58 17:58 17:20 17:20 <br /> Initial Reading(Rj): 0.0 T9 0. 0f, 0.00099 0 0009 <br /> Test End Time: 18:10 18:10 17:32 17:32 <br /> Final Read!ag(RF): 0.00019 0.0w, 0. 99 0. 090 <br /> Test Duration: 12 in 12 in 12 in 12 in <br /> Chan e in ReLd�n (RF-R,): 0.00019 0,00019 0,0001, 0.0001, <br /> Pass/Fail Threshold or Criteria: +/-.002" +/-.002" +/-.002v' +/-.002" <br /> T"t Result. X Pass ,0 F 0 FOR x PON 0 Fan x Eau—OFail <br /> Was sensor removed for testing? X Yes D No D NA X Yes 0 No D NA X Yes D No D NA X Yes D No 0 NA <br /> Was sensor properly replaced and X Yes D No 0 NA X Yes 0 No 0 NA X Yes 0 No 0 NA X Yes D No D NA <br /> verified ftinctional after te!Enj? I I <br /> Comments—(include information on repairs made prior to testiM and recommended follow-upforfailed tests) <br /> If the entire depth of the UDC is not tested,specify how much was tested. If the answer to M of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire UDC must be tested. (See SB LG-160) <br />