Laserfiche WebLink
SWRCB, January 2002 Page 5 of 7 <br />7. UNDER -DISPENSER CONTAINMENT UDC TESTING <br />Test Method Developed By: ❑ UDC Manufacturer ® Industry Standard ❑ Professional Engineer <br />❑ Other (Specify) <br />Test Method Used: ❑ Pressure ❑Vacuum ®Hydrostatic <br />❑ Other (Specify) <br />Test Equipment Used:Incon TS -STS Equipment Resolution: +/-0.0001" <br />IUDC Manufacturer: <br />UDC #23 sat <br />UDC #24sat <br />UDC #25sat <br />UDC #26 sat <br />C Material: <br />FRP <br />FRP <br />FRP <br />FRP <br />C De the <br />27" <br />27" <br />27" <br />27" <br />Height from UDC Bottom to Top <br />of Highest Piping Penetration: <br />7" <br />7" <br />7" <br />7" <br />Height from UDC Bottom to <br />Lowest Electrical Penetration: <br />5„ <br />5" <br />5" <br />4" <br />Condition of UDC prior to <br />testing: <br />Clean <br />Clean <br />Clean <br />Clean <br />Portion of UDC Tested <br />2"above highest Pipe pen <br />2"above highest Pipe pen <br />2"above highest Pipe pen <br />2"above highest Pipe pen <br />Does turbine shut down when <br />UDC sensor detects liquid (both <br />product and water)?` <br />®Yes [:]No ❑NA <br />❑Yes [:]No FNA <br />❑Yes ❑No ❑NA <br />❑Yes ❑No ❑NA <br />Turbine shutdown response time <br />Is system programmed for fail- <br />safe shutdown?* <br />®yes ❑No ❑NA <br />®Yes ❑No ❑NA <br />®Yes [:]No ❑NA <br />®Yes ❑No FNA <br />Was fail-safe verified to be <br />operational?* <br />❑Yes ❑No ® NA <br />❑Yes❑No® NA <br />❑Yes No <br />❑ ®NA <br />❑Yes ❑No ®NA <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test <br />15 Minutes <br />15 Minutes <br />15 Minutes <br />15 Minutes <br />Test Start Time: <br />4:31 <br />4:49 <br />6:02 6:36 <br />6:20 6:36 <br />7:05 7:24 <br />Initial Reading (RI): <br />3.9555 <br />1 3.9550 <br />4.4716 4.4588 <br />3.9287 3.9268 <br />2.9161 2.9162 <br />Test End Time: <br />4:46 <br />5:04 <br />6:18 6:51 <br />6:35 6:51 <br />7:21 7:39 <br />Final Reading (RF): <br />3.9549 <br />1 3.9547 <br />4.4613 4.4530 <br />3.9283 3.9265 <br />2.9160 2.9162 <br />Test Duration: <br />15 Min Each (30 Min) <br />15 Min Each (30 Min <br />15 Min Each (30 Min) <br />15 Min Each (30 Min) <br />Change in Reading (RF -Rt): <br />0.0006 1 0.0003 <br />0.0103 1 0.0186 <br />0.0004 1 0.0003 <br />0.0001 0.0000 <br />Pass/Fail Threshold or Criteria: <br />+/- 0.002" <br />+/- 0.002" <br />+/- 0.002" <br />+/- 0.002" <br />Test Result: <br />0 Pass ❑ Fail <br />❑ Pass ® Fail <br />® Pass „ ❑ Fail <br />® Pass ; ❑ Fail <br />Was sensor removed for testing? <br />®Yes [-]No ❑NA <br />®Yes [:]No ❑NA <br />®Yes ❑No FNA <br />®Yes ❑No ❑NA <br />Was sensor properly replaced and <br />verified functional after testing? <br />®Yes ❑No ❑NA <br />®Yes ❑No [:INA®Yes <br />❑No FNA <br />®Yes ❑No ❑NA <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />Under dispenser # 23,25 and 26 all passed Hydrostatic test. <br />Under dispenser # 24 sat Failed Hydrostatic test. <br />1 If the entire depth of the UDC is not tested, specify how much was tested. If the answer to any of the questions indicated with an <br />asterisk(*) is "NO" or "NA", the entire UDC must be tested. (See SWRCB LG -160) <br />