Laserfiche WebLink
SWRCB, January 2002 Page 7 of 7 <br />9. SPILL/OVERFILL CONTAINMENT BOXES <br />Facility is Not Equipped With Spill/Overfill Containment Boxes ❑ <br />Spill/Overfill Containment Boxes are Present, but were Not Tested ❑ <br />Test Method Developed By: ❑ Spill Bucket Manufacturer ® Industry Standard ❑ Professional Engineer <br />❑ Other (Specify) <br />Test Method Used: <br />❑ Pressure ❑ Vacuum ® Hydrostatic <br />❑ Other (Specify) <br />Test Equipment Used:Incon TS -STS Equipment Resolution:+/- 0.0001" <br />Spill Box #1 DSL Spill Box #2 DSL Spill Box #3 DSL Spill Box #Autodsl <br />Bucket Diameter: 16" 16" 16" 12" <br />Bucket Depth: <br />12" 12" 12" 12" <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />15 Minutes 15 Minutes 15 Minutes 15 Minutes <br />Test Start Time: <br />4:59 12:35 4:59 3:53 <br />Initial Reading (RI): <br />2.1052 3.6853 5.7623 5.7535 <br />Test End Time: <br />5:14 12:51 5:14 4:08 <br />Final Reading (RF): <br />2.1046 3.6849 5.7623 5.7355 <br />Test Duration: <br />15 Min Ea(30 Min) 15 Min Ea(30 Min) 15 Min Ea(30 Min) 15 Min Ea(30 Min) <br />Change in Reading (RF -R,): <br />0.0008 0.0004 0.0000 0.018 <br />Pass/Fail Threshold or <br />Criteria: <br />+/- 0.002" +/-0.002" +/- 0.002" +/- 0.002" <br />Test Result: ' ® Pass ❑ Fail ®- Pass ❑ Fail 1 ® Pass [:]Fail ❑, Pass ; ® Fall <br />Comments — (inchsde information on repairs made prior to testing, and recommended follow-up for failed tests) <br />Truck Tanks #1,2 & 3 fill contairmnent buckets all passed Hydrostatic test. <br />Tank #6 Auto Diesel fill containment bucket Failed hydrostatic test no visual leaks. <br />