• <br />SANsWOUIN <br />--COUNTY <br />• <br />Environmental Health Department <br />idStarage' a�� ReporE <br />Facility Name: <br />Facility Address: <br />Date: <br />FLYING J TRAVEL PLAZA #618* <br />1501 N JACK TONE RD, RIPON <br />May 03, 2018 <br />zr.. <br />Item # <br />Remarks <br />301 <br />HSC 25292.1 UST system is not operated to prevent unauthorized release, including spills and overfills. <br />Fuel filters were observed outside UDC containment on all UDC dispensers on the auto side. The underground <br />storage tank system shall be operated to prevent unauthorized releases. Immediately contact a properly licensed, <br />trained, and certified contractor to make repairs to the UST system under permit and inspection of the EHD. <br />This is a Class II violation. <br />308 <br />CCR 2636(f) Failed to maintain a continuous monitoring system that activates an audible and visual alarm. <br />The Tank #3 Diesel STP sump sensor failed to activate an audible and visual alarm when tested to ensure <br />continuous monitoring of the tank system. All monitoring equipment shall be maintained to activate an audible and <br />visual alarm or stop the flow of product at the dispenser when it detects a leak. The sensor was replaced and <br />retested during the inspection. A "UST Retrofit Verification with Inspector Already Onsite" form has been completed <br />and provided to the operator and contractor. <br />This was corrected on site. <br />This is a minor violation. <br />315 <br />HSC 25291(e) Water in secondary containment not removed, analyzed, and properly disposed of (pre -Jul 2003). <br />Liquid was observed in Tank #144 STP sumps. If water could enter into the secondary containment by <br />precipitation or infiltration, it must be removed and disposed of properly. The service technician removed about a <br />cup of liquid from the above mentioned STP sumps. Ensure that all sumps are maintained free of liquid. <br />This was corrected on site. <br />This is a repeat violation, Class II. <br />318 <br />CCR 2636(f)(2) Leak detector failed to detect a 3.0 gph leak at 10 psi. <br />The 87 line leak detector failed to detect a leak when tested. All line leak detectors shall be capable of detecting a <br />3 -gallon per hour leak at 10 psi. Immediately have a properly licensed, trained, and certified contractor repair or <br />replace the failed leak detector (LG 113-x listed, if applicable) and obtain a permit within one business day from the <br />EHD. If the failed leak detector can't be replaced immediately, there is a possibility that the 87 grade UST system <br />may be red tagged to prevent fuel inputs. <br />This is a minor violation. <br />Overall Inspection Comments: <br />An inspection checklist was provided to the facility operator on the first day of inspection, May 3, 2018. The <br />EHD has written the complete report which replaces the initial checklist on May 4, 2018. <br />Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br />documenting the corrective actions that have been or will be taken for each violation, and any supporting <br />paperwork, within 30 days of receiving the complete inspection report, June 2, 2018. <br />FA0006672 PR0505264 SCO01 05/03/2018 <br />EHD 23-01 Rev. 10/31/2017 Page 5 of 6 Underground Storage Tank Program OIR <br />1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />