Laserfiche WebLink
Page 1 of 1 <br /> SPILUOVERFILL CONTAINMENT BOXES <br /> Facility is Not Equipped With Fill Riser Containment Sumps <br /> Fill Riser Containment Sumps are Present, but were Not Tested <br /> Test Method Developed By: r Spill Bucket Manufacturer C+ Industry Standard r Professional Engineer <br /> Other(Specify): <br /> Test Method Used By: r Pressure r Vacuum r Hydrostatic <br /> Other(Specify): <br /> Test Equipment Used: ' VACUUM TEST ? Equipment Resolution: 0.1 h I <br /> Spill Box# Spilt Box <br /> 'Tank T 1PREMIUM Tank T 2 REGULAR Spill Box# Spill=Box# <br /> Fill-Direct Fill-Direct <br /> Bucket Diameter. 12.00 12.00 <br /> Bucket Depth: 13.00 13.00 <br /> Wad time between applying 1 min 1 min min min <br /> pressuretvaouum/water and starting test <br /> Test Start Time: 14:07:00 14:41:00 <br /> Initial Reading(R,): 30.00 in. H2O 30.00 in. H2O <br /> Test End Time: 14:08:00 14:42:00 <br /> Final Reading rRd: 29.00 in. H2O 26.00 in. H2O <br /> Test Duration: 1 min 1 m i n <br /> Change in Reading(RKR,): -1.00 in. H2O -4.00 in. H2O <br /> Pass/Fail Threshold or Criteria: +1-4.00 +/-4.00 +/- +/- <br /> Test Result- Pass Pass <br /> Comments?(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> WO:2309193 <br />