Chevron Monitoring Certification Checklist <br /> Store Number: 208117 Address: 755 S.TRACY BLVD TRACY,CA 95376 <br /> F <br /> Date:2/27/2013 Technician: Steven Willems Company:TANKNOLOGY INC. j <br /> Tangy 1-PREMIUM Tank 2-REGULA I <br /> Product 1 2 <br /> Tank Type <br /> (DW FRP,DW Steel,SW FRP) Fiberglass Fiberglass <br /> Tank Diameter 117.75 117.75 <br /> Annular Riser Height(measured) 78.50 77.50 <br /> Required(calculated)annular sensor length <br /> FRP tanks-see Note 1 below 184.87 184.87 <br /> Steel tanks-see Note 2 <br /> Is req'd annular sensor length marked with tape& <br /> labeled with dimension Y Y <br /> (Y/N,document w/photo)? <br /> Actual(measured)annular sensor length <br /> 248.00 271.00 <br /> (to marked point) <br /> Are the DW pipe boots pulled back in tank sumps? <br /> (YIN or N/A,note if can't be verified because clamshell is Y Y <br /> pointing down) <br /> Are tank sump sensors back in their holders and in the <br /> correct position? Y Y <br /> (YIN or N/A document with photo) <br /> _ (Y/N) Comments <br /> Has the Veeder Root Battery been replaced prior to failsafe? �� <br /> Has Veeder Root Programming before&after testing been verified? y <br /> (especially tank manifolding setup-see Note 3) <br /> Has Veeder Root Programming before&after testing been attached to the Y <br /> Work Order? <br /> € <br /> Are gasoline spin on-filters replaced during testing for ethanol per <br /> Chevron requirements n/a <br /> (Cim Tek 300MB-10 or 400MB-10 or PetroClear 40510-A only) <br /> Have all alarms generated during testing been noted in the station Alarm y <br /> Log?(YIN) <br /> Additional Comments: <br /> Note 1: DW FRP Tank Annular Calculations Note 2: DW Steel Tank Annular Calculation <br /> (circumference) <br /> X=tank diameter+Riser Height <br /> X=(3.14 x tank diam/2)+riser height <br /> 10'diameter €X=188"+riser <br /> B'diameter I X=151"+riser <br /> 6'diameter X=113"+riser <br /> Note 3:Certain Veeder Root Software versions will automatically revert to the default tank manifold settings anytime the programming is changed,such as when <br /> sensors are temporarily X'ed out,etc. <br />