7. UNDER-DISPENSER CONTAINMENT UDC TESTING <br /> Test Method Developed By: ❑UDC Manufacturer ®Industry Standard ❑Professional Engineer <br /> ❑Other(Spec) <br /> Test Method Used: ❑Pressure ❑Vacuum ®Hydrostatic <br /> ❑Other(Specify) <br /> Test Equipment Used: See attached testing procedures Equipment Resolution: Inches <br /> UDC# 1/2 UDC# 3/4 UDC# 5/6 UDC# 7/8 <br /> UDC Manufacturer: <br /> UDC Material: Fiberglass Fiberglass Fiberglass Fiberglass <br /> UDC Depth: 32" 32" 32" 32^ <br /> Height from UDC Bottom to Top 10„ 10^ 101. 10^ <br /> of Highest Piping Penetration: <br /> Height from UDC Bottom to 51. 5^ 5° 5° <br /> Lowest Electrical Penetration: <br /> Condition of UDC prior t® <br /> Fair Fair Fair Fair <br /> testing: <br /> Portion of UDC Tested Above highest penetration Above highest penetration Above highest penetration Above highest penetration <br /> Does turbine shut down when <br /> UDC sensor detects liquid(both N/A N/A N/A N/A <br /> product and water)?* <br /> Turbine shutdown response time <br /> Is system programmed for fail- ❑Yes ❑No [23 NA ❑Yes ❑No Z NA ❑Yes ❑No ®NA ❑Yes ❑No Z NA <br /> safe shutdown?` <br /> Was fail-safe verified to be <br /> oerational?" ElYes E]No p NA ❑Yes E]No p NA ❑Yes ❑No p NA E]Yes ❑No p NA <br /> Wait time between applying <br /> pressure/vacuum/water and 15 minutes 15 minutes 15 minutes 15 minutes <br /> starting test <br /> Test Start Time: 12:10pm 12:35pm 12:35pm 12:10pm <br /> Initial Reading (RI): 10.10674 Inches 5.1275 Inches 0.25278 Inches 1.33434 Inches <br /> Test End Time: 12:25pm 12:50pm 12:50pm 12:25pm <br /> Final Reading(RF): 10.10756 Inches 5.1275 Inches 0.25262 Inches 1.33452 Inches <br /> Test Duration: 15 mins 15 mins 15 mins 15 mins <br /> Change in Reading(RF-R,): 0.00082 0.0000 0.00016 0.00018 <br /> Pass/Fail Threshold or Criteria: 0.002 0.002 0.002 0.002 <br /> Test Result: 0 Pass ❑Fail Z Pass ❑Fail 2 Pass ❑Fail p Pass ❑Fail <br /> Was sensor removed for testin ? ❑Yes ❑No ❑NA ®Yes ❑No ❑NA p Yes ❑No ❑NA p Yes ❑No ❑NA <br /> Was sensor properly replaced and [2]ng? <br /> ❑No E]NA ❑Yes E]No ❑NA ❑Yes E]No F1 NA m Yes El No ❑NA <br /> verified functional after testin ? <br /> Comments—(include information on repairs made prior to testing,and recommended follow-up for failed tests) <br />