Laserfiche WebLink
SWRCB,January 2002 Page 13 <br /> 7. UNDER-DISPENSER CONTAINMENT (UDC) TESTING <br /> Test Method Developed By: UDC Manufacturer F-1 Industry Standard ❑X Professional Engineer <br /> Other (Specify) <br /> Test Method Used: FI Pressure F Vacuum Hydrostatic <br /> El Other (Specify) <br /> Test Equipment Used: vpl t Equipment Resolution: vplt to gph <br /> UDC# 16/17 UDC# 18 UDC# 19 UDC# 19sat <br /> UDC Manufacturer: W•f. W.f. W.f. W.f. <br /> UDC Material: fiberglass fiberglass fiberglass fiberglass <br /> UDC Depth: 3111 3111 311f 3111 <br /> Height from UDC Top to Top of 9 to 911 9" 911 <br /> Highest Piping Pentration: <br /> Height from UDCTop to Lowest 1/211 1/2'1 1/211 1/2'1 <br /> Electrical Pentration: <br /> Condition of UDC prior to testing: good good good good <br /> Portion of UDC Tested: 1 111, 1111 111, 1111 <br /> Does turbine shut down when <br /> sump sensor detects liquid(both X❑Yes E Yes_NoDN Yes MNo❑N M Yes F]No[:]N <br /> product and water)?* <br /> Turbine shutdown response time: 2-5sec 2-5sec 2-5sec 2-5 s e c <br /> Is system programmed for fail-safe ❑ � ❑ ❑ � ❑ '---'Yes <br /> ❑ <br /> shutdown?* X Yes N N X Yes N N X Yes N N X Yes No <br /> Was fail-safe verified to be Yes❑No❑N Yes❑N�N Yes❑No�N Yes�No�N <br /> operational? <br /> Wait time between applying <br /> pressure/vacuum/water and starting SMIN 5MIN 5MIN 5MIN <br /> test: <br /> Test Start Time: 10:57 10:55 8 :34 8:3 0 <br /> Initial Reading(Ri): 2 .132 5.754 8.358 4.702 <br /> Test End Time: 10 :59 11:10 8:4 9 8:45 <br /> Final Reading(RF): -13.000 5.754 8.358 4.702 <br /> Test Duration: 2min 15min 15min 15min <br /> Change in Reading(RF-R1 ): 1.8gph .000gph .000gph .000gph <br /> Pass/Fail Threshold or Criteria: .05gph .05gph 05gph .05gph <br /> Was sensor removed for testing? Yes❑No❑NAYes NA Yes ]No❑NA X Yes No[]N <br /> Was sensor properly replaced and ❑ � � � MyeC]NcONA <br /> ❑ ❑verified functional after testing? N NA X Ye N NA X yes N <br /> Comments - (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> 1 If the entire depth of the UDC is not tested,specify how much was tested.If the answer toanyof the questions indicated with an <br /> asterisk(*)is"NO" or"NA",the entire UDC must be tested. (See SWRCB LG-160) <br />