SWRCB,January 2002 Page of <br /> 8. FILL RISER CONTAINMENT SUMP TESTING <br /> Facility is Not Equipped With Fill Riser Containment Sums ❑ <br /> Fill Riser Containment Sumps are Present,but were Not Tested ❑ <br /> Test Method Developed By: ❑Sump Manufacturer [9 Industry Standard ❑Professional Engineer <br /> ❑Other(Specify) <br /> Test Method Used: ❑Pressure ❑Vacuum 9 Hydrostatic <br /> ❑Other(Spec) <br /> Test Equipment Used: Incon Incon TS-STS Tester Equipment Resolution: +/-0.002" <br /> Fill Sump# 91 Fill Sump# Fill Sump# Fill Sump# <br /> Sump Diameter: 36" <br /> Sump Depth: 50" <br /> Height from Tank Top to Top of 12" <br /> Highest Piping Penetration: <br /> Height from Tank Top to Lowest 23„ <br /> Electrical Penetration: <br /> Condition of sump prior to pry <br /> testing: <br /> Portion of Sump Tested 28" <br /> Sump Material: Fiber lass <br /> Wait time between applying <br /> pressure/vacuum/water and 15 minutes <br /> starting test: <br /> Test Start Time: 11:37am 12:00pm <br /> Initial Reading(RI): 5.3059" 5.3059" <br /> Test End Time: 11:52am 12:15pm <br /> Final Reading(RF): 5.3059" 5.3059" <br /> Test Duration: 15 Minutes Each 30 <br /> Chane in Reading RF-Ri): 0.0000 1 0.0000 <br /> Pass/Fail Threshold or Criteria: +/-0.002" +/-0.002" <br /> Test Result:: ® Pass 0 Fail 0 Pass 0 Fail 0 Pass 0 Fail 0 Pass 0 Fail <br /> Is there a sensor in the sump? ®Yes ❑No ❑Yes ❑No ❑Yes ❑No ❑Yes ❑No <br /> Does the sensor alarm when <br /> either product or water is ®Yes []No ❑NA ❑Yes ❑No ®NA ❑Yes ❑No ®NA ❑Yes ❑No ®NA <br /> detected? <br /> Was sensor removed for testing? ®Yes ❑No ❑NA ❑Yes ❑No ®NA ❑Yes ❑No ®NA ❑Yes ❑No ®NA <br /> Was sensor properly replaced and ®Yes ❑No ❑NA ❑Yes ❑No ®NA ❑Yes ❑No ®NA ❑Yes ❑No ®NA <br /> verified functional after testin ? <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />