Page 1 of —8 - <br />6. PIPING SUMP TESTING <br />Test Method Developed By: ❑ Sump Manufacturer ❑ Industry Standard ® Professional Engineer <br />❑ Other (Specify) <br />Test Method Used: ❑ Pressure ❑ Vacuum ®Hydrostatic <br />❑ Other (Specify) <br />Test Equipment Used: Caldwell Level Indicator <br />Equipment Resolution: .002 <br />Sump #Unleaded <br />Sump #Premium <br />Sump #Diesel <br />Sump #Vent <br />Sump Diameter: <br />42 <br />42 <br />42 <br />26 <br />Sump Depth: <br />63 <br />63 <br />63 <br />24 <br />Sump Material: <br />fiberglass <br />fiberglass <br />fiberglass <br />fiberglass <br />Height from Tank Top to Top of <br />Highest Piping Penetration: <br />14.5" <br />14.5" <br />14.5" <br />0 <br />Height from Tank Top to Lowest <br />Electrical Penetration: <br />23" <br />23" <br />23" <br />0 <br />Condition of sump prior to testing: <br />clean <br />clean <br />clean <br />clean <br />Portion of Sump Tested' <br />2"above <br />product line <br />2" above <br />product line <br />2"above <br />product line <br />1811 <br />Does turbine shut down when <br />sump sensor detects liquid (both <br />product and water)?* <br />® Yes ❑ No[-] NA <br />® Yes ❑ No ❑ NA <br />® Yes❑ No ❑ NA <br />❑ Yes® No ❑ NA <br />Turbine shutdown response time <br />n/a <br />n/a <br />n/a <br />n/a <br />Is system programmed for fail-safe <br />shutdown?` <br />® Yes ❑ No ❑NA <br />® Yes[-] No ❑ NA <br />® Yes❑ No ❑ NA <br />❑ Yes® No ❑ NA <br />Was fail-safe verified to be <br />operational?* <br />❑ yes® No ❑ NA <br />❑ Yes ® No ❑ NA <br />❑ Yes® No ❑ NA <br />❑ Yes ❑ No ® NA <br />Wait time between applying <br />pressure/vacuum/water and starting <br />test: <br />15mins <br />15mins <br />15mins <br />15mins <br />Test Start Time: <br />30mins <br />30mins <br />30mins <br />30mins <br />Initial Reading (RI): <br />first circle <br />first circle <br />first circle <br />first circle <br />Test End Time: <br />Omins <br />Orcins <br />Orcins <br />Omins <br />Final Reading (RF): <br />no change <br />no change <br />no change <br />no change <br />Test Duration: <br />30mins <br />30mins <br />30mins <br />30mins <br />Change in Reading (RF -RI): <br />0 <br />0 <br />0 <br />0 <br />Pass/Fail Threshold or Criteria: <br />.005/30mins <br />.005/30mins <br />.005/30mins <br />.005/30mins <br />Test Result: <br />® Pass ❑ Fail <br />® Pass ❑ Fail <br />® Pass ❑ Fail <br />® Pass ❑ Fail <br />Was sensor removed for testing? <br />® Yes ❑ No❑ NA <br />® Yes[:] Non NA <br />® Yes[:] No❑NA <br />® Yes ❑ No❑ NA <br />Was sensor properly replaced and <br />verified functional after testing? <br />❑ Yes ® No❑ NA <br />❑ Yes ® No❑NA <br />❑ Yes® No❑NA <br />❑ Yes ® Non NA <br />Comments - (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />All sensors are tested during annual monitoring certification. <br />I If the entire depth of the sump is not tested, specify how much was tested. If the answer to any of the questions indicated with an <br />asterisk (*) is "NO" or "NA", the entire sump must be tested. <br />