Page 1 of _8_ <br />7. UNDER -DISPENSER CONTAINMENT (UDC) TESTING <br />Test Method Developed By: ❑ UDC Manufacturer ❑ Industry Standard ® Professional Engineer <br />❑ Other (Specify) <br />Test Method Used: ❑ Pressure ❑ Vacuum ®Hydrostatic <br />❑ Other (Specify) <br />Test Equipment Used: Caldwell Level Indicator Equipment Resolution: .002 <br />UDC #1-2 <br />UDC #34 UDC #5-6 <br />UDC #7-8 <br />UDC Manufacturer: <br />opw <br />opw opw <br />opw <br />UDC Material: <br />fiberglass <br />fiberglass fiberglass <br />fiberglass <br />UDC Depth: <br />30 <br />30 30 <br />30 <br />Height from UDC Bottom to Top <br />of Highest Piping Penetration: <br />12 <br />12 12 <br />12 <br />Height from UDC Bottom to <br />Lowest Electrical Penetration: <br />14 <br />14 14 <br />14 <br />Condition of UDC prior to <br />testing: <br />clean <br />clean clean <br />clean <br />Portion of UDC Tested <br />2" above product <br />2" above product 2" above product <br />2" above product <br />Does turbine shut down when <br />UDC sensor detects liquid (both <br />product and water)?* <br />®Yes❑ No ® NA <br />®Yes❑ No ❑ NA ®Yes❑ No ❑ NA <br />®Yes❑ No ❑ NA <br />Turbine shutdown response time <br />®Yes❑ No ❑ NA <br />®Yes❑ No ❑NA ®Yes[—] No ❑ NA <br />®Yes❑ No ❑ NA <br />Is system programmed for fail- <br />safe shutdown?* <br />®yes❑ No ❑ NA <br />®Yes❑ No ❑ NA ®Yes❑ No ❑ NA <br />®Yes❑ No ❑ NA <br />Was fail-safe verified to be <br />operational?* <br />yes <br />yes yes <br />yes <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test <br />15mins <br />15mins 15mins <br />15mins <br />Test Start Time: <br />30mins <br />30mins 30mins <br />30mins <br />Initial Reading (Rj): <br />first circle <br />first circle first circle <br />first circle <br />Test End Time: <br />Omins <br />Omins Omins <br />Omins <br />Final Reading (RF): <br />no change <br />no change no change <br />no change <br />Test Duration: <br />30mins <br />30mins 30mins <br />30mins <br />Change in Reading (RF -R,): <br />0 <br />0 0 <br />0 <br />Pass/Fail Threshold or Criteria: <br />.005/30mins <br />.005/30mins .005/30mins <br />.005/60mins <br />Test Result: <br />0 Pass ❑ Fail <br />0 Pass ❑ Fail ® Pass ❑ Fail <br />® Pass E]Fail <br />Was sensor removed for testing? <br />®Yes❑ No ❑ NA <br />®Yes❑ No ❑ NA ®Yes❑ No ❑ NA <br />®Yes❑ No ❑ NA <br />Was sensor properly replaced and <br />verified functional after testing? <br />®Yes❑ No ❑ NA <br />®Yes❑ No ❑ NA ®Yes❑ No ❑ NA <br />®Yes❑ No ❑ NA <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />All sensors are tested during annual monitoring certification. <br />1 If the entire depth of the UDC is not tested, specify how much was tested. If the answer to any of the questions indicated with an <br />asterisk (*) is "NO" or "NA", the entire UDC must be tested. <br />