Laserfiche WebLink
9. AST will withstand frost-hcave XX Yes No AST is anchored to concrete wall, in a steel berm, and is <br /> located in a covered secured lubricants enclosure not submit to weather conditions <br /> 10. AST previously relocated? Yes XX No <br /> 11 . AST Corrosion Protection Tank is covered in paint, with no evidence of external corrosion. Tank has <br /> no specific corrosion protection beyond the paint. No part of the AST touches the around. The base of the <br /> AST is steel, raised 1_ inch from the steel berm floor. There is no evidence of internal corrosion taking place. <br /> Tank's construction material is carbon steel. As this tank is not in any contact with the ground, there is no <br /> need for further corrosion protection such as cathodic corrosion protection. <br /> 12. AST Spill Prevention Equipment Filling is a remote operation via external pumps. Product is not handled <br /> outside of the intended containers. Tank has secondary containment via steel berm which has adequate <br /> eoniainment capacity to contain 100% of the product of both tanks set in the berm. Pumps have a check <br /> valve to prevent sinhoning , from tank back thru i k up hQaes. Tank has continuous electronicmonitorin <br /> with BJ Enterprises 007 audible-visible alarm pt the tanks,, whichwhen actuated flash strobe light & also <br /> operate a siren alarm at 103dB. Hydraulic hose pick ups are stored uprriaht when not in use to prevent <br /> spiligge from drainage of product remaining in the hose after filling operations. The filling system also has <br /> manual ball-valve shut downs at the pumps and at the tanks. <br /> 13 . Overfill Protection : Product is not normally handled outside of intended containers. Filling operations are <br /> achieved by connecting waste coolant caddies to a quick connect device and pneumatic air connection and <br /> pumping directly from the waste coolant caddy into the tank. Pump system in steel cabinet has an electronic <br /> alarm at the pumps. The BJ Enterprises 007 audible-visual alarms, were tested & found to be in good <br /> working condition. AST product supply system has manually operated ball"valve shut downs at the pumps <br /> and also at the tanks. <br /> 14. Toxic Considerations: Antifreeze is toxic to humans and animals ._ Waste antifreeze contains heavy metals <br /> such as lead cadmium, and chromium in high enough levels to potentially make it a regulated hazardous <br /> wast so most states strictly r _ . la#e antifr ze di ttl. Antifreeze enerators and state and local programs <br /> should not dump spent antifreeze on land or discharge it into a sanitary sewer, storm drain, ditch , dry well, or <br /> septic system : dumping antifreeze can cause serious water quality problems and might harm people, pets, or <br /> wildlife. <br /> 15 . AST secondary containment (materialldesign/listed) AST has secondary containment via steel berm to <br /> completely capture any leaks from primary vessel. Secondary containment was inspected , is intact and AST <br /> is suitable for continued usage. AST sits within a secured -covered lubricants enclosure . Leak detection is <br /> visually ascertained via visual inspection of secondary containment area. Steel thickness of the secondary <br /> containment was measured to . 109 in. steel thickness average. 20 points were measured on the berm. The <br /> berm SgUtainment capacity is 598 gals. gross containmenL with 456 als. containment after displacement. <br /> 16. Damage to AST or systems. No damage reported by Owner/OMrator. Upon_ inspection, no evidence of <br /> weld breaks, punctures, cracks , or other structural damage to the tank. _ Leak detection is assured via <br /> inspections of the secondar containment. Steel thickness of the primary vessel was measured to . 109 in . <br /> average. Steel thickness of the berm was measured to . 109 in. average. <br />