Laserfiche WebLink
combustible liquids shall be stored in a room <br />outside an approved storage cabinet. <br />2. Quantities of flammable and combustible liquid in <br />excess of 15 gallons shall be stored in an NFPA <br />and Underwriter's Laboratory approved metal <br />storage cabinet. <br />3. Not more than 60 gallons of flammable or 120 <br />gallons of combustible liquids shall be stored in <br />any one storage cabinet. <br />4. Not more than three such cabinets may be located <br />in a single storage area. <br />5. At least two portable fire extinguishers -having -a <br />rating greater than 20:ABC shall be located <br />outside of, but not more__than .10 ..feet from the <br />door opening into any room used for storage of <br />...more than 60 gallons of flammable or combustible <br />liquids. <br />Ir 9 SERVICEAND REFUELING AREAS <br />C <br />A. Flammable or combustible liquids shall be stored in <br />approved closed containers, in tanks located in <br />aboveground portable tanks. <br />B. The dispensing hose shall be an approved type. <br />C. The dispensing nozzle shall be an approved automatic - <br />closing type with a latch -open device. <br />D. The engines of all equipment being fueled shall be shut <br />off 'during the fueling operation. <br />E. Each service or fueling area shall be provided with at <br />least two fire extinguishers having a rating greater <br />than 20:ABC located so that an extinguisher will be <br />within 75 feet of each pump. <br />F. Tank cars and trucks being loaded or unloaded and <br />flammable storage tanks and system shall be properly <br />bonded and grounded. <br />FP -6 <br />